User Manual

<8. Device Information>
8-6
IM 01C25T02-01E
Table 8.11 Action of each parameters in failure mode related Function block
ALARM
Display
Cause of Alarm
Object
block
BLOCK_ERR OUT.STATUS
AL.30
HI.HI
LO.LO
Hi_Hi or Lo_Lo Alarm occurs in AI1
Function block
AI1 Depends on specied High High(Lo Lo)
Priority (*1)
AL.31
HI.HI
LO.LO
Hi_Hi or Lo_Lo Alarm occurs in AI2
Function block
AI2 Depends on specied High High(Lo Lo)
Priority (*1)
AL.32
HI.HI
LO.LO
Hi_Hi or Lo_Lo Alarm occurs in AI3
Function block
AI3 Depends on specied High High(Lo Lo)
Priority (*1)
AL.33
HI.HI
LO.LO
Hi_Hi or Lo_Lo Alarm occurs in PID
Function block
PID Depends on specied High High(Lo Lo)
Priority (*1)
AL.43
AI O/S
AI1 block is O/S mode AI1 Out-of-Service BAD-Out of Service
AL.44
AI O/S
AI2 block is O/S mode AI2
AL.45
AI O/S
AI3 block is O/S mode AI3
AL.46
NO.SCHD
AI1 block is not scheduled AI1 HOLD HOLD
AL.47
NO.SCHD
AI2 block is not scheduled AI2
AL.48
NO.SCHD
AI3 block is not scheduled AI3
AL.70
PID O/S
PID.MAN
NO.SCHD
PID block is not scheduled or is MAN,
O/S mode
PID Depends on cause of Alarm Depends on cause of Alarm
AL.71
SC O/S
SC MAN
NO.SCHD
SC block is not scheduled or is MAN,
O/S mode
SC Depends on cause of Alarm Depends on cause of Alarm
AL.72
IT O/S
IT MAN
NO.SCHD
IT block is not scheduled or is MAN,
O/S mode
IT Depends on cause of Alarm Depends on cause of Alarm
AL.73
IS O/S
IS MAN
NO.SCHD
IS block is not scheduled or is MAN,
O/S mode
IS Depends on cause of Alarm Depends on cause of Alarm
AL.74
AR O/S
AR MAN
NO.SCHD
AR block is not scheduled or is MAN,
O/S mode
AR Depends on cause of Alarm Depends on cause of Alarm
AL.90
AI SML
Simulation function of AI1 block is
active
AI1 Simulate Active Specied Status
AL.91
AI SML
Simulation function of AI2 block is
active
AI2 Simulate Active Specied Status
AL.92
AI SML
Simulation function of AI3 block is
active
AI3 Simulate Active Specied Status
AL.93
AI MAN
AI1 block is MAN mode AI1 Depends on setting condition of
STATUS_OPT Limit Status:Constant
AL.94
AI MAN
AI2 block is MAN mode AI2 Depends on setting condition of
STATUS_OPT Limit Status:Constant
AL.95
AI MAN
AI3 block is MAN mode AI3 Depends on setting condition of
STATUS_OPT Limit Status:Constant
(*1) Priority:
0 = the associated alert will never occur.
1 = the associated alert is not sent as a notication. If the priority is above 1, then the alert must be reported.
2 = Block alarm and update event have a xed priority of 2.
3-7 = advisory alarms (PV.STATUS = Active Advisory Alarm)
8-15 = critical alarms (PV.STATUS = Active Critical Alarm)