8.2 Status of Each Parameter in Failure Mode
Following tables summarize the value of EJX parameters when LCD display indicates an Alaram.
Table 8.9 Action of each parameters in failure mode related Resource block and Sensor Transducer block
ALARM
Display
Cause of Alarm
Resource
block
SENSOR Transducer block*
BLOCK_ERR BLOCK_ERR XD_ERROR PV.STATUS
SV.STATUS
TV.STATUS
CAP_TEMP_
VAL.STATUS
AMP_TEMP_
VAL.STATUS
AL.01
CAP.ERR
Pressure
Sensor problem
other I/O Failure BAD:Sensor
Failure
BAD:Sensor
Failure
Capsule
Temperature
Sensor problem
other I/O Failure BAD:Sensor
Failure
Capsule
memory
problem
Lost NV Date BAD:Device
Failure
BAD:Device
Failure
BAD:Device
Failure
BAD:Device
Failure
AL.02
AMP.ERR
Amplier
Temperature
Sensor problem
other Electronics
Failure
BAD:Sensor
Failure
Amplier
memory
problem
Lost NV Date
Lost Static
Data
BAD:Device
Failure
BAD:Device
Failure
BAD:Device
Failure
BAD:Device
Failure
Amplier
problem
other Electronics
Failure
BAD:Device
Failure
BAD:Device
Failure
BAD:Device
Failure
BAD:Device
Failure
AL.10
PRESS
Input Pressure
is outside
measurement
range limit of
capsule
UNCERTAIN:
Sensor
Conversion
not Accurate
UNCERTAIN
Subnormal
AL.11
ST.PRSS
Static Pressure
exceeds limit
UNCERTAIN
Subnormal
UNCERTAIN:
Sensor
Conversion
not Accurate
AL.12
CAP.TMP
Capsule
Temperature is
out of range
UNCERTAIN
Subnormal
UNCERTAIN
Subnormal
UNCERTAIN:
Sensor
Conversion
not Accurate
AL.13
AMP.TMP
Amplier
Temperature is
out of range
UNCERTAIN:
Sensor
Conversion
not Accurate
AL.20
NOT.RDY
No
communication
is found with
LAS.
AL.40
RS O/S
Resource Block
is in O/S mode
Out of
Service
BAD:
Non-specic
BAD:
Non-specic
BAD:
Non-specic
BAD:
Non-specic
AL.41
TB O/S
Sensor TB is in
O/S mode
Out of
Service
Out of
Service
BAD:Out of
Service
BAD:Out of
Service
BAD:Out of
Service
BAD:Out of
Service
AL.50
P.SDEV
P.ZDEV
Trimming
range error
for differential
pressure span
other Calibration
error
UNCERTAIN:
Engineering
Unit Range
Violation
AL.51
SP.SDEV
SP.ZDEV
Trimming range
error for static
pressure span
other Calibration
error
UNCERTAIN:
Engineering
Unit Range
Violation
*: For FLG_TEMP_VAL.STATUS, refer to A8.3.5.
Table 8.10 Action of each parameters in failure mode related LCD display
ALARM
Display
Cause of Alarm
LCD TB
BLOCK_ERR XD_ERROR
AL.79
LCD.RNG
LCD.CFG
Displayed value exceeds limit or LCD conguration error other Conguration Error