User Manual

<8. Device Information>
8-3
IM 01C25T02-01E
Table 8.5 Contents of DEVICE_STATUS_5
(index 1049)
Hexadecimal
Display
through DD
Description
NAMUR
NE-107
category
0x80000000 Diff Pressure
Span Trim
Error
(AL-50)
Trimming range
error for differential
pressure span
C
0x40000000 Diff Pressure
Zero Trim
Error
(AL-50)
Trimming range
error for differential
pressure zero
C
0x20000000 Static
Pressure
Span Trim
Error
(AL-51)
Trimming range
error for static
pressure span C
0x10000000 Static
Pressure
Zero Trim
Error
(AL-51)
Trimming range
error for static
pressure zero C
Table 8.6 Contents of DEVICE_STATUS_6
(index 1050)
Hexadecimal
Display
through DD
Description
NAMUR
NE-107
category
0x80000000 PID in O/S
Mode (AL-
70)
PID block is in O/S
mode
C
0x40000000 PID in MAN
Mode (AL-
70)
PID block is in MAN
mode
C
0x20000000 PID Not
Scheduled
(AL-70)
PID block is not
Scheduled
C
0x10000000 PID in
Bypass
Mode
PID Block is in
Bypass mode.
C
0x08000000 SC in O/S
Mode (AL-
71)
SC block is in O/S
mode
C
0x04000000 SC in MAN
Mode (AL-
71)
SC block is in MAN
mode
C
0x02000000 SC Not
Scheduled
(AL-71)
SC block is not
scheduled
C
0x01000000 IT in O/S
Mode (AL-
72)
IT block is in O/S
mode
C
0x00800000 IT in MAN
Mode (AL-
72)
IT block is in MAN
mode
C
0x00400000 IT Not
Scheduled
(AL-72)
IT block is not
scheduled
C
0x00100000 IS in O/S
Mode (AL-
73)
IS block is in O/S
mode
C
0x00080000 IS in MAN
Mode (AL-
73)
IS block is in MAN
mode
C
Hexadecimal
Display
through DD
Description
NAMUR
NE-107
category
0x00040000 IS Not
Scheduled
(AL-73)
IS block is not
scheduled
C
0x00020000 AR in O/S
Mode (AL-
74)
AR block is in O/S
mode
C
0x00010000 AR in MAN
Mode (AL-
74)
AR block is in MAN
mode
C
0x00008000 AR Not
Scheduled
(AL-74)
AR block is not
scheduled
C
0x00000004 IT Total
Backup Err
(AL-78)
IT Total Backup
has failed. Last IT
Output Value (IT.
LAST.VALUE) is
not saved.
F
0x00000002 LCD Display
Outside
Range Limit
(AL-79)
Displayed value
exceeds limit
C
0x00000001 LCD Display
Cong Error
(AL-79)
Specied settings
for Display do not
meet the conditions
C
Table 8.7 Contents of DEVICE_STATUS_7
(index 1051) (Applicable for option
code "DG1".)
Hexadecimal
Display
through DD
Description
NAMUR
NE-107
category
0x00004000 Flg Temp
High Alarm
(AL-87)
Flange
Temperature High
Alarm occurs.
M
0x00002000
Flg Temp
Low Alarm
(AL-87)
Flange
Temperature Low
Alarm occurs.
M
0x00001000
Outside
Diagnosis
Range (AL-
89)
Outside Diagnosis
Range.
0x00000800
Invalid Ref
fDP (AL-88)
VALUE_FDP
under normal
conditions is not
up to the reference
uctuation
level required
to blockage
detection.
C
0x00000400
Invalid Ref
fSPl (AL-88)
VALUE_FSPL
under normal
conditions is not
up to the reference
uctuation
level required
to blockage
detection.
C