User Manual
    <7.  In-Process Operation>
7-4
IM 01C25T02-01E
7.3  Simulation Function
The simulation function simulates the input of a 
function block and lets it operate as if the data was 
received from the transducer block. It is possible to 
conduct testing for the downstream function blocks 
or alarm processes.
A SIMULATE_ENABLE switch is mounted in 
the transmitter amplier. This is to prevent the 
accidental operation of this function. When this is 
switched on, simulation is enabled. (See Figure 
7.2.) To initiate the same action from a remote 
terminal, if REMOTE LOOP TEST SWITCH is 
written to the SIM_ENABLE_MSG parameter 
(index 1044) of the resource block, the resulting 
action is the same as is taken when the above 
switch is on. Note that this parameter value is 
lost when the power is turned OFF. In simulation 
enabled status, an alarm is generated from the 
resource block, and other device alarms will be 
masked; for this reason the simulation must be 
disabled immediately after using this function.
The SIMULATE parameter of AI block consists of 
the elements listed in Table 7.3 below.
Table 7.3  SIMULATE Parameter
Subindex Parameters Description
1 Simulate Status Sets the data status to 
be simulated.
2 Simulate Value Sets the value of the 
data to be simulated.
3 Transducer Status Displays the data status 
from the transducer 
block. It cannot be 
changed.
4 Transducer Value Displays the data value 
from the transducer 
block.It cannot be 
changed.
5 Simulate  
En/Disable
Controls the simulation 
function of this block. 
1: Simulation disabled 
(standard) 
2: Simulation started
When Simulate En/Disable in Table 7.3 above is 
set to 2, the applicable function block uses the 
simulation value set in this parameter instead of 
the data from the transducer block. This setting can 
be used for propagation of the status to the trailing 
blocks, generation of a process alarm, and as an 
operation test for trailing blocks.
F0702.ai
Amplifier Assembly
1
2
O
N
"OFF" during operation
Write lock switch
SIMULATE_ENABLE
Figure 7.2  SIMULATE_ENABLE Switch Position
7.4   Write lock (Write-protect) 
function
The transmitter is provided with a write lock (write-
protect) function to restrict write operations to 
blocks and prevent inadvertent writing of parameter 
data. To enable this function, use the write lock 
switch (Hard W Lock) or the WRITE_LOCK (index 
1034) (Soft W Lock). 
The CPU assembly of the transmitter is provided 
with a write lock switch (switch 2 in Figure 7.3). 
Setting switch 2 to On activates the write lock 
function, to prevent changes to block parameters 
of WRITE_LOCK_LEVEL (index 1064). Table 7.4 
shows how WRITE_LOCK_LEVEL relates to the 
block targeted by write lock. In the factory default 
setting, WRITE_LOCK_LEVEL is “2” (preventing 
writing to the transducer block, resource block and 
function block). To enable the switch lock function, 
set "Hard W Lock” (bit 4) of FEATURE_SEL (index 
1018) to “1” (On). (The factory default for “Hard W 
Lock” (bit 4) is “0” (Off). 










