User Manual
    <7.  In-Process Operation>
7-3
IM 01C25T02-01E
Table7.2  Field Diagnostic Alert
Indication of FD_*_ACTIVE Indication of FD_RECOMMEN_ACT Solution
Electronics failure Repair electronics Replace electrical parts e.g. amplier. 
Or contact sales ofce or service center.
Sensor/Actuator failure Repair Sensor/Actuator Replace mechanics e.g. sensor or 
actuator. Or contact sales ofce or service 
center.
Potential failure Investigate failure Perform reconguration, cleaning, wiring/
connector or electrical board check. 
If alarm still persists, contact sales ofce or 
service center.
Backup function in operation Repair primary side Repair primary sensor before backup 
sensor fails.
Firmware update error Retry updating rmware Retry rmware update. Check cause of the 
failure if alarm persists.
Communication conguration error Congure communication correctly Correct conguration of communication.
Non-operating-state Wait for a while Wait for a while. Check cause of the failure 
if alarm persists.
Calibration warning Check calibration Investigate cause of failure and recalibrate 
device.
Device conguration error Congure device correctly Correct conguration relating to sensor or 
actuator.
Function restricted Conrm the state Check if this is right state.
Simulation mode Conrm the state Check if this is right state.
Manual mode Conrm the state Check if this is right state.
Function Block notice Check Function Block status Check conditions of function blocks. In 
order to avoid alarm from unused function 
blocks, congure RESOURCE2.FD_
EXTENDC_MAP_n (n: 1 to 3) parameter.
Sensor/Actuator out of range Check specication Check specication of sensor and 
actuator. Or process conditions may be 
temporarily non-conforming.
Out of operating limit Check environment Check environment specication of sensor 
and actuator. Or process environment may 
be temporarily non-conforming.
Temporal decrease of value quality Check process or peripherals Check process and peripherals conditions.
Deterioration estimated by Time 
Based Maintenance
Check deterioration Check if maintenance is required.
Deterioration estimated by 
Condition Based Maintenance
Check deterioration Check if maintenance is required.
Impulse Line Blockage Detected Check process and impulse line 
condition
1.Check process and impulse line 
condition.
2.If there are large ow change or the 
change of uid under the measured 
process conditions, obtain the 
reference value again.(Please follow 
the operation procedure in User 
Manual)
Heat Trace Warning Detected Check the heater failure 1.Check the heater failure.
2.Check the capsule temp. and Amplier 
temp.
3.Adjust Flg Temp Coef(STB.FLG_
TEMP_COEF).
Optional function conguration error Check optional conguration Check conguration of optional functions.
Alarm related information Conrm information Check the alarm related information.
Process alarm Check process Check process conditions.
CHECK CHECK Check both modes for the SENSOR and 