    <5. Conguration>
5-2
IM 01C25T02-01E
5.2  Network Denition
Before connection of devices with Fieldbus, dene 
the Fieldbus network. Allocate PD Tag and node 
addresses to all devices (excluding such passive 
devices as terminators).
The PD Tag is the same as the conventional 
one used for the device. Up to 32 alphanumeric 
characters may be used for denition. Use a 
hyphen as a delimiter as required.
The node address is used to specify devices for 
communication purposes. Because this data is 
too long for a PD Tag, the host uses the node 
address in place of the PD Tag for communication. 
A range of 20 to 247 (or hexadecimal 14 to F7) can 
be set. The device (LM device) with bus control 
function (Link Master function) is allocated from 
a smaller address number (20) side, and other 
devices (BASIC device) without bus control function 
allocated from a larger address number (247) side 
respectively. Place the transmitter in the range of 
the BASIC device. When the transmitter is used as 
Link Master, place the transmitter in the range of the 
LM device. Set the range of addresses to be used 
to the LM device. Set the following parameters.
Table 5.1  Parameters for Setting Address Range
Symbol Parameters Description
V (FUN) First-Unpolled-
Node
Indicates the address 
next to the address range 
used for the host or other 
LM device.
V (NUN) Number-of-
consecutive-
Unpolled-Node
Unused address range
The devices within the address range written 
as “Unused” in Figure 5.1 cannot be used on a 
Fieldbus. For other address ranges, the range is 
periodically checked to identify when a new device 
is mounted. Care must be taken to keep the unused 
device range as narrow as possible so as to lessen 
the load on the Fieldbus.
0xF7
0xF8
0xFB
0xFC
0xFF
V(FUN)
V(FUN)+V(NUN)
LM device
Unused V(NUN)
BASIC device
Default address
Portable device address
F0501.ai
Not used
0x00
0x0F
0x10
0x13
0x14
Bridge device
Figure 5.1  Available Range of Node Addresses
To ensure stable operation of Fieldbus, determine 
the operation parameters and set them to the LM 
devices. While the parameters in Table 5.2 are to 
be set, the worst-case value of all the devices to 
be connected to the same Fieldbus must be used. 
Refer to the specication of each device for details. 
Table 5.2 lists DPharp specication values.
Table 5.2  Operation Parameter Values of the 
DPharp to be Set to LM Devices
Symbol Parameters
Description and 
Settings
V (ST) Slot-Time Indicates the time 
necessary for immediate 
reply of the device. Unit of 
time is in octets (256 μs).
Set maximum 
specication for all 
devices. For the 
transmitter, set a value of 
4 or greater.
V (MID) Minimum-Inter-
PDU-Delay
Minimum value of 
communication data 
intervals. Unit of time is in 
octets (256 μs). Set the 
maximum specication 
for all devices. For the 
transmitter, set a value of 
4 or greater.
V (MRD) Maximum-
Reply-Delay
The worst case time 
elapsed until a reply is 
recorded. The unit is 
Slottime; set the value 
so that V (MRD) × V 
(ST) is the maximum 
value of the specication 
for all devices. For the 
transmitter, the setting 
must be a value of 12 or 
greater.