User Manual

<2. Handling Cautions>
2-7
IM 01C25T02-01E
Note 3. Installation should be in accordance with
Canadian Electrical Code Part I and local
Electrical Code.
Note 4. Do not alter drawing without authorization
from CSA.
Electrical Data:
Rating 1 (Entity)
For Groups A, B, C, D, E, F, and G or Group IIC
Ui (vmax) = 24 V dc
Ii (Imax) = 250 mA
Pi (Pmax) = 1.2 W
Ci = 3.52 nF
Li = 0 μH
or
Rating 2 (FISCO)
For Groups A, B, C, D, E, F, and G or Group IIC
Ui (vmax) = 17.5 V dc
Ii (Imax) = 380 mA
Pi (Pmax) = 5.32 W
Ci = 3.52 nF
Li = 0 μH
or
Rating 3 (FISCO)
For Groups C, D, E, F, and G or Group IIB
Ui (vmax) = 17.5 V dc
Ii (Imax) = 460 mA
Pi (Pmax) = 5.32 W
Ci = 3.52 nF
Li = 0 μH
Installation requirements;
Po Pi Uo Ui Io Ii,
Co Ci + Ccable Lo Li + Lcable
Vmax Voc Imax Isc
Ca Ci + Ccable La Li + Lcable
Uo, Io, Po, Co, Lo,Voc, Isc, Ca and La are
parameters of barrier.
Caution for CSA Non-incendive type.
(Following contents refer to “DOC. No.
ICS018)
Installation Diagram for Non-incendive
or Type of protection "n" (Division 2
Installation)
Non-Hazardous location
Hazardous location
F0206.ai
Terminator
CSA Certified
Equipment [nL]
Pressure
Transmitter
SUPPLY
Terminator
+
Transmitter
+
Transmitter
+
+
+
Note 1. Installation should be in accordance with
Canadian Electrical Code Part I and local
Electrical Code.
Note 2. Dust-tight conduit seal must be used when
installed in class II and III environments.
Note 3. Do not alter drawing without authorization
from CSA.
Electrical Data:
Rating (including FNICO)
Ui or Vmax = 32 V
Ci = 3.52 nF
Li = 0 μH