User Manual

<Appendix 8. Advanced Diagnostics>
A8-20
IM 01C25T02-01E
Checklist (4/5)
No. Items Parameters Result Example
10-a-2 Low Side Blocking
Close the low-pressure side valve
completely.
Record the values of VALUE_# after
the certain time, (DIAG_PERIOD ×
DIAG_COUNT), passed.
*: Record the value after checked that
the status isGOOD”.
VALUE_FDP (Index: 2086) * 7.48562e-9
VALUE_FSPL (Index: 2087) * 7.23277e-9
VALUE_FSPH (Index: 2088) 7.14085e-9
VALUE_BLKF (Index: 2089) * -0.287259
Record the status of Checkbox in
DIAG_OPTION.
Check that the alarms status of “A
BlockingandLow Side Blocking” are
set.
Note: If the alarm of “Outside Diagnosis
Range” is generated, the valve may
be closed too much tightly. Open
valve a little and record the updated
status of the parameters.
DIAG_OPTION (Index: 2072)
A Blocking
Large Fluctuation of Low Side
Large Fluctuation of High Side
Low Side Blocking
High Side Blocking
B Blocking
Invalid Ref BlkF
Invalid Ref fSPh
Invalid Ref fSPl
Invalid Ref fDP
Outside Diagnosis Range
Reect Blockage to PV/SV/TV
Status
Check that the alarm of “Low Side
Blockingis generated.
Check that the alarm of “High Side
Blockingis not generated.
DIAG_ERR (Index: 2069)
Low Side Blocking
High Side Blocking
10-a-3 Both Side Blocking
Close the both-pressure side valves
completely.
Record the values of VALUE_# after
the certain time, (DIAG_PERIOD ×
DIAG_COUNT), passed.
*: Record the value after checked that
the status isGOOD”.
VALUE_FDP (Index: 2086) 7.48562e-9
VALUE_FSPL (Index: 2087) 7.23277e-9
VALUE_FSPH (Index: 2088) 7.14085e-9
VALUE_BLKF (Index: 2089) -0.287259
Record the status of Checkbox in
DIAG_OPTION.
Check that the alarms status of “High
Side Blocking, “Low Side Blocking
and “B Blocking” are set.
Note: If the alarm of “Outside Diagnosis
Range” is generated, the valve may
be closed too much tightly.
Open valve a little and record the
updated status of the parameters.
DIAG_OPTION (Index: 2072)
A Blocking
Large Fluctuation of Low Side
Large Fluctuation of High Side
Low Side Blocking
High Side Blocking
B Blocking
Invalid Ref BlkF
Invalid Ref fSPh
Invalid Ref fSPl
Invalid Ref fDP
Outside Diagnosis Range
Reect Blockage to PV/SV/TV
Status
Check that the alarm of “B Blocking” is
generated.
DIAG_ERR (Index: 2069)
B Blocking