    <Appendix 8. Advanced Diagnostics>
A8-19
IM 01C25T02-01E
Checklist (3/5)
Go to the following step according to the result of "Invalid Ref xx" shown in the DIAG_ERR of 8th check item.
DIAG_ERR (Index: F2086)
Check item
Invalid Ref fSPh Invalid Ref fSPl Invalid Ref fdP
  
10-a
  
10-b
: The alarm is generated.
: The alarm is not generated.
No. Items Parameters Result Example
10-a Simulation of Blockage detection 
operation
•  High Side Blocking: 10-a-1
•  Low Side Blocking: 10-a-2
•  Both Side Blocking: 10-a-3
10-a-1 High Side Blocking
•  Close the high-pressure side valve 
completely.
•  Record the values of VALUE_# after 
the certain time, (DIAG_PERIOD × 
DIAG_COUNT), passed.
*: Record the value after checked that 
the status is “GOOD”.
VALUE_FDP (Index: 2086)* 7.48562e-9
VALUE_FSPL (Index: 2087) * 7.23277e-9
VALUE_FSPH (Index: 2088) * 7.14085e-9
VALUE_BLKF (Index: 2089) -0.287259
•  Record the status of Checkbox in 
DIAG_OPTION.
•  Check that the alarms status of “A 
Blocking” and “High Side Blocking” 
are set.
Note: If the alarm of “Outside Diagnosis 
Range” is generated, the valve may 
be closed too much tightly. Open 
valve a little and record the updated 
status of the parameters.
DIAG_OPTION (Index: 2072)
A Blocking
 
Large Fluctuation of Low Side
 
Large Fluctuation of High Side
 
Low Side Blocking
 
High Side Blocking
 
B Blocking
 
Invalid Ref BlkF
 
Invalid Ref fSPh
 
Invalid Ref fSPl
 
Invalid Ref fDP
 
Outside Diagnosis Range
 
Reect Blockage to PV/SV/TV 
Status
 
•  Check that the alarm of “High Side 
Blocking” is generated.
•  Check that the alarm of “Low Side 
Blocking” is not generated.
DIAG_ERR (Index: 2069)
High Side Blocking
 
Low Side Blocking
 