User Manual

<Appendix 8. Advanced Diagnostics>
A8-10
IM 01C25T02-01E
A8.2.5.5 Reect Blockage to PV/SV/TV
Status
“Reect Blockage to PV/SV/TV Status
corresponding to bit 15 in DIAG_OPTION is
used to link the alarm to the OUT signal status of
PRIMARY_VALUE, SECONDARY_VALUE, and
TERTIARY_VALUE.
When the ILBD algorithm detects the abnormality,
each signal status becomes “UNCERTAIN: Non
Specic”.
The alarm is linked to the signal status of PV, SV
and TV, according to the following procedure.
1) Set "Stop" to DIAG_MODE.
2) Check the checkbox of “Availability for the
Statusof DIAG_OPTION.
Note:Set to “Calculation” after setting the parameters.
NOTE
The alarms of "Invalid Ref xx", "Outside
Diagnosis Range" do not link to the signal status
of PV, SV, and TV.
A8.2.6 Condition Check
After the EJX differential pressure/pressure
transmitter was installed, it is necessary to conrm
that the Primary Value (PV) is stable under the
normal operating condition and that uctuation
amplitude under the normal operating condition is
large enough to detect the blockage.
A8.2.6.1 Stability of Primary Value
1) Observe the value change of PRIMARY_
VALUE under the normal operating condition
for 10 minutes.
2) Conrm the value change is less than 10%.
If the value change is more than 10%, the error
inuences pressure uctuation value so that the
blockage detection becomes Unreliable. You need
to consider the plant operating conditions.
A8.2.6.2 Fluctuation Value
NOTE
The blockage detection may not be carried
out correctly when pressure uctuation
amplitude especially with the pressure and level
measurement, is small.
Conrm that each value of VALUE_FDP, VALUE_
FSPL, VALUE_FSPH, and VALUE_BLKF is more
than the value specied in the below table.
Table A8.3 Requiremnents to apply ILBD
Condition
VALUE_FDP 7×10
-10
or more
VALUE_FSPL 1×10
-10
or more
VALUE_FSPH 1×10
-10
or more
VALUE_BLKF -0.5 to 0.5
VALUE_FDP is not enough
No blockage can be detected if VALUE_FDP is not
larger than the specied value.
Only VALUE_FDP is enough
“A Blocking” or B Blocking” can be detected if
VALUE_FSPL and VALUE_FSPH are not larger
than specied values.
VALUE_FDP and VALUE_FSPL are enough
“High Side Blocking” andLarge Fluctuation of High
Side” can not be detected if VALUE_FSPH is not
larger than specied value.
VALUE_FDP and VALUE_FSPH are enough
“Low Side Blocking” and “Large Fluctuation of Low
Side” can not be detected if VALUE_FSPL is not
larger than specied value.
VALUE_FDP, VALUE_FSPL and VALUE_FSPH
are enough
All alarm modes can be detected even if VALUE_
BLKF is not within the specied values.
A8.2.7 Obtain Reference Values
The pressure uctuation values are reduced
when the impulse line is plugged. Therefore, the
reference value is required to determine the degree
of reduction