A7.6  Steps after Activating a 
Field Device
When the communication with a eld device has 
recovered after activating the device, check using 
the download tool that the software revision of the 
eld device has been updated accordingly.  The 
value of SOFT_REV of the resource block indicates 
the software revision.
The PD tag, node address, and transducer block 
calibration parameters that are retained in the 
nonvolatile memory inside the target device will 
remain unchanged after a software download.  
However, after a software update which causes an 
addition to the block parameters or blocks, or to the 
system/network management VFD parameters, 
some parameters may be reset to the defaults, thus 
requiring parameter setup and engineering again.  
For details, see the table below.
Also note that a change in the number of 
parameters or blocks requires the DD and 
capabilities les corresponding to the new software 
revision.
Table A7.1  Actions after Software Update
Contents of Software 
Update
Action
Does not change the number 
of parameters.
Re-setup of parameters 
not needed.
Adds a block parameter. Setup of the added 
parameter needed.
Adds a block. Reengineering and 
setup of the added 
block’s parameters 
needed.
Changes the number of 
system/network management 
VFD parameters.
Reengineering needed.
A7.7  Troubleshooting
For information on the download tool’s error messages, see also the software’s User’s Manual.
Table A7.2  Problems after Software Update
Symptom Cause Remedy
An error occurs before starting a 
download, disabling the download.
The selected download le is not for 
the selected eld device.
Check SOFTDWN_ERROR in the 
resource block and obtain the correct le.
An error occurs after starting a 
download, disabling the download.
You attempted to update the device 
revision by downloading a le which is 
not an original le.
Check SOFTDWN_ERROR in the 
resource block and obtain the original le.
The selected eld device does not 
support software downloading.
Check whether the option code /EE is 
included in the model and sufx codes of 
the device.
The voltage on the eldbus segment 
falls below the specied limit (9 volts).
Check the capacity of the eld bus power 
supply used and the voltage at the terminal.
There was an error in a checksum or 
the number of transmission bytes.
Check SOFTDWN_ERROR in the 
resource block and obtain the correct le.
The download tool does not allow 
download with same software revision.
Check the setting of the download tool.
The download takes far longer than 
expected or fails frequently.
The eldbus segment is noisy. Check the noise level on the eldbus 
segment.
An error occurs after activation. Transient error caused by the internal 
resetting of the eld device.
Check whether communication with the 
eld device has recovered after a while.
The new software does not work 
after the activation.
The le of the current revision was 
downloaded.
Obtain the correct le.
Failure of the memory in eld device, 
etc.
Check SOFTDWN_ERROR in the 
resource block, and re-try downloading.
If fails, place a service call.