User Manual
    <Appendix 6.  Link Master Functions>
A6-4
IM 01C25T02-01E
A6.5  LM Parameters
A6.5.1  LM Parameter List
The tables below show LM parameters.  
Meanings of Access column entries: RW = read/write possible; R = read only
Index
(SM)
Parameter Name
Sub-parameter Name
(Sub Index)
Default Factory
Setting
Access Remarks
375 PLME_BASIC_
CHARACTERISTICS
0 R
1 ChannelStatisticsSupported 0x00
2 MediumAndDataRatesSupported 0x4900000000000000
3 IecVersion 1 (0x1)
4 NumOfChannels 1 (0x1)
5 PowerMode 0 (0x0)
376 CHANNEL_STATES 0 R
1 channel-1 0 (0x0)
2 channel-2 128 (0x80)
3 channel-3 128 (0x80)
4 channel-4 128 (0x80)
5 channel-5 128 (0x80)
6 channel-6 128 (0x80)
7 channel-7 128 (0x80)
8 channel-8 128 (0x80)
377 PLME_BASIC_INFO 0 R
1 InterfaceMode 0 (0x0)
2 LoopBackMode 0 (0x0)
3 XmitEnabled 1 (0x1)
4 RcvEnabled 1 (0x1)
5 PreferredReceiveChannel 1 (0x1)
6 MediaTypeSelected 73 (0x49)
7 ReceiveSelect 1 (0x1)
378 DLME_LINK_MASTER_CAPABILITIES_VARIABLE 0x04 RW
379 DLME_LINK_
MASTER_INFO_
RECORD
0 RW
1 MaxSchedulingOverhead 0
2 DefMinTokenDelegTime 100
3 DefTokenHoldTime 300
4 TargetTokenRotTime 4096
5 LinkMaintTokHoldTime 400
6 TimeDistributionPeriod 5000
7 MaximumInactivityToClaimLasDelay 2
8 LasDatabaseStatusSpduDistributionPeriod 6000
380 PRIMARY_LINK_MASTER_FLAG_VARIABLE 0 RW LAS: True = 0xFF; 
non-LAS: False = 0x00
381 LIVE_LIST_STATUS_ARRAY_VARIABLE 0 R
382 MAX_TOKEN_
HOLD_TIME_
ARRAY
0 RW
1 Element1 0x0000(x16), 
0x012C(x16)
2 Element2 0x012C(x5), 
0x0000(x27)
3 Element3 0x0000(x32)
4 Element4 0x0000(x32)
5 Element5 0x0000(x32)
6 Element6 0x0000(x32)
7 Element7 0x0000(x31), 
0x012C(x1)
8 Element8 0x012C(x32)
383 BOOT_OPERAT_FUNCTIONAL_CLASS Specied at the time 
of order
RW 0x01 (basic device); 
0x02 (LM)