User Manual
    <Appendix 5.  PID Block>
A5-9
IM 01C25T02-01E
NOTE:  If a control block is connected as a cascade primary 
block of the PID block in question, a mode transition of 
the PID block to Cas occurs in the following sequence 
due to initialization of the cascade connection: RCas or 
ROut → Auto → Cas.  
A5.18  Alarms
There are two kinds of alarms generated by a PID 
block: block and process alarms.  
A5.18.1  Block Alarm (BLOCK_ALM)
The block alarm BLOCK_ALM is generated upon 
occurrence of either of the following errors (values 
set in BLOCK_ERR) and noties the content of 
BLOCK_ERR.  
Value of
BLOCK_ERR
Condition
Local Override MODE_BLK actual of PID block is LO.
Input Failure The status of PV is Bad. (The status 
of IN is Bad, or the status of IN is 
Uncertain and “Use Uncertain as Good” 
is false in STATUS_OPTS.)
Out of Service MODE_BLK.target of the PID block is 
O/S.
A5.18.2  Process Alarms
There are six types of process alarms. Only one 
process alarm can be generated at the same time, 
and the process alarm having the highest priority 
level from among those occurring at the same 
time is generated.  The priority level is set for each 
process alarm type.  
Process 
Alarm
Cause of Occurrence
Parameter 
Containing 
Priority Level 
Setting
HI_HI_ALM Occurs when the PV 
increases above the 
HI_HI_LIM value.
HI_HI_PRI
HI_ALM Occurs when the PV 
increases above HI_LIM 
value.
HI_PRI
LO_ALM Occurs when the PV 
decreases below the 
LO_LIM value.
LO_PRI
LO_LO_
ALM
Occurs when the PV 
decreases below the 
LO_LO_LIM value.
LO_LO_LIM
DV_HI_ALM Occurs when the value of 
[PV - SP] increases above 
the DV_HI_LIM value.
DV_HI_PRI
DV_LO_
ALM
Occurs when the value 
of [PV - SP] decreases 
below the DV_LO_LIM 
value.
DV_LO_PRI
A5.19  Example of Block 
Connections
PID
BKCAL_IN OUT
IN
AO
BKCAL_OUT
CAS_IN
AI
OUT
FA0506.ai
When conguring a simple PID control loop by 
combining an EJX transmitter with a eldbus 
valve positioner that contains an AO block, follow 
the procedure below to make the settings of the 
corresponding eldbus function blocks: 
1. Connect the AI block and PID block of the EJX, 
and the AO block of the valve positioner as 
shown above.  
2. Set MODE_BLK.target of the PID block to 
O/S, and then set GAIN, RESET, and RATE to 
appropriate values.  
3. Check that the value of MODE_BLK.actual of 
the AI block is Auto.  
4. Set MODE_BLK.target of the AO block to 
CAS|AUTO (meaning "Cas and Auto").  
5. Check that the value of BKCAL_IN.status of the 
PID block is not Bad.  
6. Check that the value of IN.status of the PID 
block is not Bad.
7. Check that Auto is set in MODE_BLK.permitted 
of the PID block.  
8. Set MODE_BLK.target of the PID block to Auto. 
When nishing all steps in order, the PID block and 
AO block exchange the respective information and 
initialize the cascade connection.  Consequently, 
the value of MODE_BLK.actual of the PID block 
changes to Auto and automatic PID control starts.  










