User guide

<5. Modbus Communication>
5-13
IM 01C25R05-01EN
Address
Label used in
DTM
Address Type Access Type
Char/
Date
Read/
Write
Enum list
Default
Value
*1
Unit
Valid
Range
IM
Chapter
1947 Disp User Value
Point 15
Holding
Register
USIGN8 - W Table 88 0x0001 - 0 to 4 3.4.3
1948 Disp User Value
Point 16
Holding
Register
USIGN8 - W Table 88 0x0001 - 0 to 4 3.4.3
2001 Engr Select Holding
Register
USIGN8 - W Table 89 0x0000 - 0 to 2 3.4.3
2002-
2005
Engr Unit Holding
Register
USIGN32×2 ASCII W - spaces - - 3.4.3
2006 Engr exp Holding
Register
USIGN8 - W Table 90 0x0000 - 0 to 3 3.4.3
2007 Engr URV Holding
Register
FLOAT - W - 100.0 - - 3.4.3
2009 Engr LRV Holding
Register
FLOAT - W - 0.0 - - 3.4.3
2011 Engr point Holding
Register
USIGN8 - W Table 88 0x0001 - 0 to 4 3.4.3
2012 Set Engr Unit Holding
Register
USIGN8 - W Table 91 0x0000 - 0 to 45 3.4.3
2051 Pres Alert Mode
Holding
Register
USIGN8 - W Table 92 0x0000 - 0 to 3 3.4.7
2052 Pres Hi Alert Val Holding
Register
FLOAT - W - 100.0 kPa -110 to
110
3.4.7
2054 Pres Lo Alert Val Holding
Register
FLOAT - W - -100.0 kPa -110 to
110
3.4.7
2056 SP Alert Mode Holding
Register
USIGN8 - W Table 92 0x0000 - 0 to 3 3.4.7
2057 SP Hi Alert Val Holding
Register
FLOAT - W - 25.0 MPa -2.5 to
27.5
3.4.7
2059 SP Lo Alert Val Holding
Register
FLOAT - W - 0.0 MPa -2.5 to
27.5
3.4.7
2061 ET Alert Mode Holding
Register
USIGN8 - W Table 92 0x0000 - 0 to 3 3.4.7
2062 ET Hi Alert Val Holding
Register
FLOAT - W - 850.0 °C -200 to
850
3.4.7
2064 ET Lo Alert Val Holding
Register
FLOAT - W - -200.0 °C -200 to
850
3.4.7
2101 Flow Simulation
Mode
Holding
Register
USIGN8 - W Table 93 0x0000 - With in
enum list
3.4.8
2102 Flow Sim Pres
Unit
Holding
Register
USIGN8 - W
Table 60 0x000C - With in
enum list
3.4.8
2103 Flow Sim Pres Holding
Register
FLOAT - W - 0.0 kPa -1600 to
1600
3.4.8
2105 Flow Sim SP
Unit
Holding
Register
USIGN8 - W Table 61 0x000C - With in
enum list
3.4.8
2106 Flow Sim SP Holding
Register
FLOAT - W - 0.0 kPa -400000
to 400000
3.4.8
2108 Flow Sim Temp
Unit
Holding
Register
USIGN8 - W Table 62 0x0023 - With in
enum list
3.4.8
2109 Flow Sim Temp Holding
Register
FLOAT - W - 273.15 K - 3.4.8
2111 Sim Device
Variable Code
Holding
Register
USIGN8 - W Table 94 0x0001 - 1 to 3 3.4.8
2112 Sim Write
Device Variable
Code
Holding
Register
USIGN8 - W Table 95 0x0000 - 0 to 1 3.4.8
2113 Sim Unit Code Holding
Register
USIGN8 - W Table
60, 61, 62
0x0000 - With in
enum list
3.4.8
2114 Sim Device
Variable Value
Holding
Register
FLOAT - W - 0.0 - - 3.4.8
2116 Sim Device
Variable Status
Holding
Register
USIGN8 -
W Table 5 0x0000 - With in
enum list
3.4.8
2117 Test Auto
Release Time
Holding
Register
USIGN8 - W Table 96 0x0000 - 0 to 5 3.4.8
*1: This value is factory default of M range measurement span without order specication.
*2: Upper case character can be used. Lower-case is translated to upper case.