User guide

<5. Modbus Communication>
5-8
IM 01C25R05-01EN
Address
Label used in
DTM
Address Type Access Type
Char/
Date
Read/
Write
Enum list
Default
Value
*1
Unit
Valid
Range
IM
Chapter
1132-
1139
Extra No. Holding
Register
USIGN32×4 ASCII
*2
R - spaces - -
1140 Final asmbly
num
Holding
Register
USIGN24 - W -
0x00000000
- -
1142-
1149
PT100 Serial
No.
Holding
Register
USIGN32×4 ASCII
*2
W - spaces - -
1150 Country Holding
Register
USIGN16 ASCII W - “JP” - -
1151 Auto recover Holding
Register
USIGN8 - W Table 33 0x0001 - 0 to 1
1152 Isoltr matl Holding
Register
USIGN8 - W Table 34 - - With in
enum list
1153 Fill uid Holding
Register
USIGN8 - W Table 35 - - With in
enum list
1154 Gasket matl Holding
Register
USIGN8 - W Table 36 - - With in
enum list
1155 Process Conn
matl
Holding
Register
USIGN8 - W Table 37 - - With in
enum list
1156 Drain vent matl
Holding
Register
USIGN8 - W Table 38 - - With in
enum list
1157 Process Conn
type
Holding
Register
USIGN8 - W Table 39 - - With in
enum list
1158 RS isoltr matl Holding
Register
USIGN8 - W Table 40 - - With in
enum list
1159 Process Conn
size
Holding
Register
USIGN8 - W Table 41 - - With in
enum list
1160 Num of RS Holding
Register
USIGN8 - W Table 42 - - With in
enum list
1161 RS ll uid Holding
Register
USIGN8 - W Table 43 - - With in
enum list
1162 RS type Holding
Register
USIGN8 - W Table 44 - - With in
enum list
1351 Slave Address Holding
Register
USIGN8 - W - 0x0001 - 1 to 247 3.2
1352 Stop Bit Holding
Register
USIGN8 - W Table 55 0x0000 - 0 to 1 3.2
1353 Parity Holding
Register
USIGN8 - W Table 56 0x0000 - 0 to 2 3.2
1354 Turnaround
Delay Time
Holding
Register
USIGN16 - W - 0x000A - 0x000A to
0x00C8
3.2
1401 Pres Unit Holding
Register
USIGN8 - W Table 60 0x000C - With in
enum list
3.3.4
1402 SP Unit Holding
Register
USIGN8 - W Table 61 0x00ED - With in
enum list
3.3.4
1403 ET Unit Holding
Register
USIGN8 - W Table 62 0x0020 - With in
enum list
3.3.4
1421 SP H/L Select Holding
Register
USIGN8 - W Table 70 0x0000 - 0 to 1 3.4.1
1422 A/G Select Holding
Register
USIGN8 - W Table 71 0x0001 - 0 to 1 3.4.1
1423 Atm. Pres Value Holding
Register
FLOAT - W - 0.101325 MPa -2.5 to
27.5
1451 Pres URV Holding
Register
FLOAT - W - 100.0 kPa -110 to
110
3.3.3
1453 Pres LRV Holding
Register
FLOAT - W - 0.0 kPa -110 to
110
3.3.3
1455 SP URV Holding
Register
FLOAT - W - 16.0 MPa -2.5 to
27.5
3.3.3
1457 SP LRV Holding
Register
FLOAT - W - 0.0 MPa -2.5 to
27.5
3.3.3
1459 ET URV Holding
Register
FLOAT - W
- 850.0 °C -210 to
860
3.3.3
*1: This value is factory default of M range measurement span without order specication.
*2: Upper case character can be used. Lower-case is translated to upper case.