User guide
    <5.  Modbus Communication>
5-8
IM 01C25R05-01EN
Address
Label used in 
DTM
Address Type Access Type
Char/ 
Date
Read/ 
Write
Enum list
Default 
Value
*1
Unit
Valid 
Range
IM 
Chapter
1132- 
1139
Extra No. Holding 
Register
USIGN32×4 ASCII
*2
R - spaces - -
1140  Final asmbly 
num
Holding 
Register
USIGN24 - W -
0x00000000
- -
1142- 
1149
PT100 Serial 
No.
Holding 
Register
USIGN32×4 ASCII
*2
W - spaces - -
1150  Country Holding 
Register
USIGN16 ASCII W - “JP” - -
1151  Auto recover Holding 
Register
USIGN8 - W Table 33 0x0001 - 0 to 1
1152  Isoltr matl Holding 
Register
USIGN8 - W Table 34 - - With in 
enum list
1153  Fill uid Holding 
Register
USIGN8 - W Table 35 - - With in 
enum list
1154  Gasket matl Holding 
Register
USIGN8 - W Table 36 - - With in 
enum list
1155  Process Conn 
matl
Holding 
Register
USIGN8 - W Table 37 - - With in 
enum list
1156  Drain vent matl
Holding 
Register
USIGN8 - W Table 38 - - With in 
enum list
1157  Process Conn 
type
Holding 
Register
USIGN8 - W Table 39 - - With in 
enum list
1158  RS isoltr matl Holding 
Register
USIGN8 - W Table 40 - - With in 
enum list
1159  Process Conn 
size
Holding 
Register
USIGN8 - W Table 41 - - With in 
enum list
1160  Num of RS Holding 
Register
USIGN8 - W Table 42 - - With in 
enum list
1161  RS ll uid Holding 
Register
USIGN8 - W Table 43 - - With in 
enum list
1162  RS type Holding 
Register
USIGN8 - W Table 44 - - With in 
enum list
1351  Slave Address Holding 
Register
USIGN8 - W - 0x0001 - 1 to 247 3.2
1352  Stop Bit Holding 
Register
USIGN8 - W Table 55 0x0000 - 0 to 1 3.2
1353  Parity Holding 
Register
USIGN8 - W Table 56 0x0000 - 0 to 2 3.2
1354  Turnaround 
Delay Time
Holding 
Register
USIGN16 - W - 0x000A - 0x000A to 
0x00C8
3.2
1401  Pres Unit Holding 
Register
USIGN8 - W Table 60 0x000C - With in 
enum list
3.3.4
1402  SP Unit Holding 
Register
USIGN8 - W Table 61 0x00ED - With in 
enum list
3.3.4
1403  ET Unit Holding 
Register
USIGN8 - W Table 62 0x0020 - With in 
enum list
3.3.4
1421  SP H/L Select Holding 
Register
USIGN8 - W Table 70 0x0000 - 0 to 1 3.4.1
1422  A/G Select Holding 
Register
USIGN8 - W Table 71 0x0001 - 0 to 1 3.4.1
1423  Atm. Pres Value Holding 
Register
FLOAT - W - 0.101325 MPa -2.5 to 
27.5
1451  Pres URV Holding 
Register
FLOAT - W - 100.0 kPa -110 to 
110
3.3.3
1453  Pres LRV Holding 
Register
FLOAT - W - 0.0 kPa -110 to 
110
3.3.3
1455  SP URV Holding 
Register
FLOAT - W - 16.0 MPa -2.5 to 
27.5
3.3.3
1457  SP LRV Holding 
Register
FLOAT - W - 0.0 MPa -2.5 to 
27.5
3.3.3
1459  ET URV Holding 
Register
FLOAT - W
- 850.0 °C -210 to 
860
3.3.3
*1:  This value is factory default of M range measurement span without order specication.
*2:  Upper case character can be used. Lower-case is translated to upper case.