User guide

<5. Modbus Communication>
5-6
IM 01C25R05-01EN
5.7.2 Address Map (Detail Information)
Address
Label used in
DTM
Address Type Access Type
Char/
Date
Read/
Write
Enum list
Default
Value
*1
Unit
Valid
Range
IM
Chapter
1001 Restart Coil SINGLE BIT - W Table 1 0 - 0x0000,
0xFF00
1002 Squawk Coil SINGLE BIT - W Table 1 0 - 0x0000,
0xFF00
3.4.8
1003 Error log Clear Coil SINGLE BIT - W Table 1 0 - 0x0000,
0xFF00
1004 Auto Atm. Pres Coil SINGLE BIT - W Table 1 0 - 0x0000,
0xFF00
1005 Reset cfg chng
count
Coil SINGLE BIT - W Table 1 0 - 0x0000,
0xFF00
4.1.3
1001-
1008
Status group 1 Discrete Input SINGLE
BIT×8
- R Table 6 - - - 4.1.1
1009-
1016
Status group 2 Discrete Input SINGLE
BIT×8
- R Table 7 - - - 4.1.1
1017-
1024
Status group 3 Discrete Input SINGLE
BIT×8
- R Table 8 - - - 4.1.1
1025-
1032
Status group 4 Discrete Input SINGLE
BIT×8
- R Table 9 - - - 4.1.1
1033-
1040
Status group 5 Discrete Input SINGLE
BIT×8
- R Table 10 - - - 4.1.1
1041-
1048
Status group 6 Discrete Input SINGLE
BIT×8
- R Table 11 - - - 4.1.1
1049-
1056
Status group 7 Discrete Input SINGLE
BIT×8
- R Table 12 - - - 4.1.1
1057-
1064
Status group 8 Discrete Input SINGLE
BIT×8
- R Table 13 - - - 4.1.1
1065-
1072
Status group 9 Discrete Input SINGLE
BIT×8
- R Table 14 - - - 4.1.1
1073-
1080
Status group 10 Discrete Input SINGLE
BIT×8
- R Table 15 - - - 4.1.1
1081-
1088
Status group 11 Discrete Input SINGLE
BIT×8
- R Table 16 - - - 4.1.1
1001 Distributor Input Register USIGN16 - R - 0x0037 - -
1002 Device Type
Code
Input Register USIGN16 - R - 0x0054 - -
1003 Fld dev rev Input Register USIGN8 - R - - - -
1004 Software rev Input Register FLOAT -
R - - - -
1006-
1013
Model Input Register USIGN32×4 ASCII R - - - -
1014 Write protect Input Register USIGN8 - R Table 31 0x0000 - - 3.4.6
1015 Software seal Input Register USIGN8 - R Table 32 0x0001 - -
1025 Cfg chng count Input Register USIGN8 - R - - - - 4.1.3
1101 Pres Input Register FLOAT - R - - - - 3.3.2
1103 SP Input Register FLOAT - R - - - - 3.3.2
1105 ET Input Register FLOAT - R - - - - 3.3.2
1107 Pres Data
Quality
Pres Limit
Status
SP Data Quality
SP Limit Status
Input Register USIGN16 - R Table 5 - - - 4.1.3
1108 ET Data Quality
ET Limit Status
Reserved
Input Register USIGN16 - R Table 5 - - - 4.1.3
1109 Status group 1
Status group 2
Input Register USIGN16 - R Table 6
Table 7
- - - 4.1.1
1110 Status group 3
Status group 4
Input Register USIGN16 - R Table 8
Table 9
- - - 4.1.1
1111 Status group 5
Status group 6
Input Register USIGN16 - R Table 10
Table 11
- - - 4.1.1
*1: This value is factory default of M range measurement span without order specication.
*2: Upper case character can be used. Lower-case is translated to upper case.