User guide
    <5.  Modbus Communication>
5-6
IM 01C25R05-01EN
5.7.2  Address Map (Detail Information)
Address
Label used in 
DTM
Address Type Access Type
Char/ 
Date
Read/ 
Write
Enum list
Default 
Value
*1
Unit
Valid 
Range
IM 
Chapter
1001  Restart Coil SINGLE BIT - W Table 1 0 - 0x0000, 
0xFF00
1002  Squawk Coil SINGLE BIT - W Table 1 0 - 0x0000, 
0xFF00
3.4.8
1003  Error log Clear Coil SINGLE BIT - W Table 1 0 - 0x0000, 
0xFF00
1004  Auto Atm. Pres Coil SINGLE BIT - W Table 1 0 - 0x0000, 
0xFF00
1005  Reset cfg chng 
count
Coil SINGLE BIT - W Table 1 0 - 0x0000, 
0xFF00
4.1.3
1001- 
1008
Status group 1 Discrete Input SINGLE 
BIT×8
- R Table 6 - - - 4.1.1
1009- 
1016
Status group 2 Discrete Input SINGLE 
BIT×8
- R Table 7 - - - 4.1.1
1017- 
1024
Status group 3 Discrete Input SINGLE 
BIT×8
- R Table 8 - - - 4.1.1
1025- 
1032
Status group 4 Discrete Input SINGLE 
BIT×8
- R Table 9 - - - 4.1.1
1033- 
1040
Status group 5 Discrete Input SINGLE 
BIT×8
- R Table 10 - - - 4.1.1
1041- 
1048
Status group 6 Discrete Input SINGLE 
BIT×8
- R Table 11 - - - 4.1.1
1049- 
1056
Status group 7 Discrete Input SINGLE 
BIT×8
- R Table 12 - - - 4.1.1
1057- 
1064
Status group 8 Discrete Input SINGLE 
BIT×8
- R Table 13 - - - 4.1.1
1065- 
1072
Status group 9 Discrete Input SINGLE 
BIT×8
- R Table 14 - - - 4.1.1
1073- 
1080
Status group 10 Discrete Input SINGLE 
BIT×8
- R Table 15 - - - 4.1.1
1081- 
1088
Status group 11 Discrete Input SINGLE 
BIT×8
- R Table 16 - - - 4.1.1
1001  Distributor Input Register USIGN16 - R - 0x0037 - -
1002  Device Type 
Code
Input Register USIGN16 - R - 0x0054 - -
1003  Fld dev rev Input Register USIGN8 - R - - - -
1004  Software rev Input Register FLOAT -
R - - - -
1006-
1013
Model Input Register USIGN32×4 ASCII R - - - -
1014  Write protect Input Register USIGN8 - R Table 31 0x0000 - - 3.4.6
1015  Software seal Input Register USIGN8 - R Table 32 0x0001 - -
1025  Cfg chng count Input Register USIGN8 - R - - - - 4.1.3
1101  Pres Input Register FLOAT - R - - - - 3.3.2
1103  SP Input Register FLOAT - R - - - - 3.3.2
1105  ET Input Register FLOAT - R - - - - 3.3.2
1107  Pres Data 
Quality
Pres Limit 
Status 
SP Data Quality
SP Limit Status
Input Register USIGN16 - R Table 5 - - - 4.1.3
1108  ET Data Quality
ET Limit Status
Reserved
Input Register USIGN16 - R Table 5 - - - 4.1.3
1109  Status group 1 
Status group 2
Input Register USIGN16 - R Table 6 
Table 7
- - - 4.1.1
1110  Status group 3 
Status group 4
Input Register USIGN16 - R Table 8
Table 9
- - - 4.1.1
1111  Status group 5 
Status group 6
Input Register USIGN16 - R Table 10 
Table 11
- - - 4.1.1
*1:  This value is factory default of M range measurement span without order specication.
*2:  Upper case character can be used. Lower-case is translated to upper case.