User guide
    <4.  Diagnostics>
4-4
IM 01C25R05-01EN
Integral 
Indicator
DTM 
display
Status 
group
Cause Countermeasure
Value and Status (Data Quality and Limit Status)
Differential 
Pressure 
(DP)
Static 
Pressure 
(SP)
External  
Temperature 
(ET)
DP % SP % ET %
AL.35 
P. HI
P high 
alarm
5 Input pressure 
exceeds 
specied 
threshold.
Check input. Value:
Measured value
Status:
Good and Not Limited
(0xC0)
Value:
Measured value
Status:
Good and Not Limited
(0xC0)
AL.36 
P. LO
P low 
alarm
AL.37 
SP. HI
SP high 
alarm
Input static 
pressure 
exceeds 
specied 
threshold.
AL.38 
SP. LO
SP low 
alarm
AL.43 
ET. HI
ET high 
alarm
8 Input external 
temperature 
exceeds 
specied 
threshold.
AL.44 
ET. LO
ET low 
alarm
AL.50 
P. LRV
Illegal P 
LRV
6 Specied value 
is outside of 
setting range.
Check settings 
and change 
them as 
needed.
Value:
Measured value
Status:
Good and Not Limited
(0xC0)
Value: 
Hold value
Status: 
Bad and 
Constant
(0x30)
Value:
Measured value
Status:
Good and Not Limited
(0xC0)
AL.51 
P. URV
Illegal P 
URV
AL.52 
P. SPN
Illegal P 
SPAN
AL.53 
P. ADJ
P SPAN 
trim err
Adjust settings 
and change 
them as 
needed.
Value:
Measured 
value
Status:
Poor 
Accuracy 
and Not 
Limited
(0x40)
Value:
Measured value
Status:
Good and Not Limited
(0xC0)
Value:
Measured 
value
Status:
Poor 
Accuracy 
and Not 
Limited
(0x40)
Value:
Measured value
Status:
Good and Not Limited
(0xC0)
P ZERO 
trim err
AL.54 
SP. RNG
Illegal SP 
LRV
Check settings 
and change 
them as 
needed.
Value:
Measured value
Status:
Good and Not Limited
(0xC0)
Value:
Measured 
value
Status:
Good 
and Not 
Limited
(0xC0)
Value: 
Hold value
Status: 
Bad and 
Constant
(0x30)
Value:
Measured 
value
Status:
Good 
and Not 
Limited
(0xC0)
Illegal SP 
URV
Illegal SP 
SPAN