User guide
    <4.  Diagnostics>
4-1
IM 01C25R05-01EN
4.  Diagnostics
4.1  Self-Diagnostics
4.1.1   Identify Problems by Using the 
Conguration Tool
The conguration tool can be used to run self-
diagnostics on a transmitter and check for incorrect 
data settings.
The Status menu is available for self-diagnostics.
If the specic diagnostic item is known for the 
check, you can directly call up the item by using the 
Status menu. 
The status is categorized from 1 to 11.
See Table 4.1 to determine the status group.
Show an example below to conrm the status of 
Status group 1.
•  Procedure to call up the Status display
[Root Menu] → Diag/Service → Status → Status group 1
If no error is detected, check mark is cleared on the 
conguration tool.
If there is an error, “check mark” is displayed on the 
conguration tool, and a countermeasure for that 
error is necessary.
In addition to Status group 1-11 parameters, 
Status Bytes parameter in Address Map (Basic 
Information) is available. 
[Root Menu] →Diag/Service → Status 
→ Status Bytes Status information only mapped in 
Address Map (Basic Information)
4.1.2  Checking with Integral Indicator
NOTE
If an error is detected by running self-diagnostics, 
an error number is displayed on the integral 
indicator. If there is more than one error, the error 
number changes at three-second intervals.
See Table 4.1 regarding the alarm codes.
F0401.ai
Figure 4.1  Integral Indicator
4.1.3  Status Information 
(1)  Data quality and Limit status
EJX multivariable transmitter can handle 
Device Variables (DP(Pres), SP, ET. Each 
variable contains data quality and limit status 
for providing useful status about the data value. 
The data quality is normally “Good”. However, 
in the case of a sensor failure or out of 
measurement range, it turns to “Bad” or “Poor 
Accuracy”. The limit status indicates whether 
the data value is limited (i.e., not responding 
to the process). When the limit status is 
“Constant”, the value will not be changed. For 
detail, refer to Table 4.1 and 4.2.
•  Procedure to call up the display 
[Device Variables]
[Root Menu] → Process variables → Device variables 
and Status → 
→ Press Data 
Quality
Good, Poor Accuracy, Manual/
Fixed, or Bad is displayed.
→ press Limit 
Status
Constant, Low Limit, High Limit, or 
Not Limited is displayed.
It is the same about the SP and ET.
(2)  Conguration Change Counter
The Conguration Change Counter is 
incremented once for every user action 
that changes the device’s conguration or 
calibration. This value is never reset or written 
and maintained even if power is removed from 
the device. 
•  Procedure to call up the display 
[Root Menu] → Diag/Service → Status →  
→ Cfg chng 
count
The conguration change times 
are counted. 
(3)  Reset Conguration Change Counter
Conguration Change Counter can be reset by 
this method.
•  Procedure to call up the display 
[Root Menu] → Diag/Service → Status → Reset Cfg 
Chng Count