User guide
    <3.  Parameter Setting>
3-15
IM 01C25R05-01EN
(2)  Device Variable Simulation Function 
Using the simulation function, the output signal can 
be conrmed by setting any value and status to the 
selected device variable.
Call up the parameter and follow the message 
shown.
After completing the step 5, the simulation starts.
Integral indicator shows output and alarm (AL.91) 
alternately.
•  Procedure of device variable simulation
Step 1 Call up the 
parameter 
[Root Menu] → Diag/
Service → Test → Simulate
2 Selection of 
Device Variable
Select one parameter from 
the list below
 Off
 Pres
 SP
 ET
3 Setting of Value Input the simulate value
4 Setting of Data 
quality
Select one parameter from 
the list below
 Bad
 Poor accuracy
 Manual / Fixed
 Good
5 Setting of Limit 
status
Select one parameter from 
the list below
 Not limited
 Low limited
 High limited
 Constant
NOTE
•  All the simulations for differential pressure, 
static pressure and external temperature, 
are reected to the output. Accordingly, 
LCD display, and communication output are 
directly corresponded to the simulate value. 
The alarm output is also available according 
to the simulate value.
•  Damping is applicable for differential 
pressure, static pressure, and external 
temperature simulation.
(3)  Squawk 
This feature can be used to identify the 
communicating transmitter by remotely causing 
LCD to display the particular pattern as shown in 
the Figure 3.3.
“SQUAWK” continues for approximately 10 
seconds, then is released automatically.
•  Procedure to call up the Squawk display
[Root Menu] → Diag/Service → Test → Squawk
P
S P
T
F
F0307.ai
Figure 3.3  LCD display for Squawk