User guide
    <3.  Parameter Setting>
3-10
IM 01C25R05-01EN
a.   Display Selection
At Disp select, select the variable that the 
parameter Disp 1 will display on the integral 
indicator. 
•  Procedure to call up the display
[Root Menu] → Detailed setup → Display condition → 
Disp select → 
→ Disp Out 1 Select desired display from ve kinds 
of displays shown above.
Set Disp OUT 2 to 16 in the same way if necessary.
“Not used” is also displayed as a selection item.
b.  Cyclic Display 
Displays can be displayed cyclically in the order of 
the parameter number. 
c.  Display Resolution
User can change the position of decimal point 
which is shown on the integral indicator.
•  Procedure to call up the Disp % reso display
[Root Menu] → Detailed setup → Display condition →
→  Disp % 
Reso
Select the decimal point position of %
Normal: Display one digit below the 
decimal point
High Resolution: Display two digits 
below the decimal point
•  Procedure to call up the Pres disp point, SP 
disp point and ET disp point display
[Root Menu] → Detailed setup → Display condition → 
Disp Condition →
→  Pres disp 
point
Select the decimal point position of 
differential pressure  (0, 1, 2, 3 or 4)
→  SP disp 
point
Select the decimal point position of 
static pressure  (0, 1, 2, 3 or 4)
→ET disp point Select the decimal point position of 
external temperature   (0, 1, 2, 3 or 4)
d.  User Setting of Engineering Unit and Scale
Engr disp range parameters allow the engineering 
unit and scale to be displayed. At Set Engr Unit, 
the following engineering units can be selected from 
a list.  
•  Procedure to call up the display
[Root Menu] → Detailed setup → Display condition → 
Engr disp range
→  Set Engr 
Unit
Select the engineering unit
→  Engr LRV Lower range value
→  Engr URV Upper range value
→  Engr exp Exponents for user scale display
→  Engr point Decimal point position for user scale 
display
→  Engr unit Conrm and set unit
→  Engr Select Select the target of Engineering unit
Select the engineering unit from the list. Available 
units are shown below
kPa
MPa
mbar
bar
psi
psia
mmH
2
O
mmHg
mmHgA
mmAq
mmWG
Torr
inH
2
O
inHg
inHgA
ftH
2
O
gf/cm
2
kgf/cm
2
kg/cm
2
G
kg/cm
2
A
atm
kg/h
t/h
m
3
/h
m
3
/min
l/h
l/min
kl/h
kl/min
Nl/h
Nl/min
Nm
3
/h
Nm
3
/min
ACFH
ACFM
CFH
SCFM
GPH
GPM
m
mm
in
ft
kg/m
3
g/cm
3
At Engr Unit parameter, user can conrm and set 
your own unit also. 
Up to eight alphanumeric characters, spaces or one 
slashe (/) can be input at Engr Unit; only the rst six 
are displayed on the integral indicator.   
•  Procedure to call up the display
[Root Menu] → Detailed setup → Display condition → 
Engr disp range → 
→  Engr Unit Set your own unit 
Note that following symbols are not available: 
  #   %   &   <  >   .  *   :   +   -  ,   ’  (   )
The integral indicator shows “-- -- -- -- -- --” when 
these symbols or more than two slashes are 
entered.
e.   External input values and information
16 external input values corresponds to “Disp User 
Value 1-16” selection lists and they can be selected 
from 16 integral indicator display “Disp Out 1-16” 
parameters. Regarding the Procedure to call up the 
display, refer to “a. Display Selection”.
External input value can be set to oating variable 
parameter “Disp User Value 1-16” parameters 
and external input information1 can be set to 8 
characters variable “Disp User Info 1_1-16_1” 
parameters.
External input information2 can be set into 8 
characters variable “Disp User Info 1_2-16_2.”
User can change the position of decimal point 
which is shown on the integral indicator by “Disp 
User Value Point 1-16” parameters.