    <3.  Parameter Setting>
3-7
IM 01C25R05-01EN
3.3  Basic Setup
3.3.1  Tag and Device Information
If there are specied when ordering, the desired Tag 
No. and device information are set and shipped. 
Tag No. and device information can be checked as 
follows.
•  Procedure to call up the display 
Item Procedure
Tag [Root Menu] → Basic setup → Tag 
→ Tag
Long Tag
[Root Menu] → Basic setup → Tag 
→ Long Tag
Descriptor [Root Menu] → Basic setup → Device 
information → Descriptor
Message [Root Menu] → Basic setup → Device 
information → Message
Date [Root Menu] → Basic setup → Device 
information → Date
When the Tag No. and device information are 
changed, input them based on the following 
limitations.
Item Limitations
Tag Up to 8 characters or numbers*
1
Long tag
Up to 32 characters or numbers*
2
Descriptor Up to 16 characters or numbers*
1
Message Up to 32 characters or numbers*
1
Date mm/dd/yyyy
- mm: month (2 digits)
- dd: days (2 digits)
- yyyy: years (4 digits)
*1:   The characters bounded by the thick line in the following 
table can be used.
*2:   All characters in the following table can be used.
SP ! " # $ % & ' ( ) * + , - . /
0 1 2 3 4 5 6 7 8 9 : ; < = > ?
@ A B C D E F G H I J K L M N O
P Q R S T U V W X Y Z [ \ ] ^ _
` a b c d e f g h i j k l m n o
p q r s t u v w x y z { | } ~
*:  SP shows one-byte space
3.3.2  Process Variables 
Process Variables and Status are monitored 
by following menus. The status information is 
explained in “4. Diagnostics.”
•  Procedure to call up the display
Item Procedure
• Press, SP, ET
• % range of Press, SP, ET
[Root Menu] 
Process Variables and 
Status
[Root Menu] → Process 
variables → Process 
variables → Device 
Variable and Status
3.3.3  Measuring Range 
This section shows how to conrm and change 
the parameters for measuring range of differential 
pressure, static pressure, and external temperature, 
and also unit and damping time constant. 
These parameters are set at the factory before 
shipment if specied at the time of order.
Follow the procedure below to change them. 
About the differential pressure, static pressure and 
external temperature, settable range are shown 
on the parameters of LSL (Lower settable limit), 
USL (Upper settable limit) and Min span (Minimum 
span). Set the data within the range.
•  Procedure to call up the display 
Call up and setting of differential pressure related 
parameters
[Root Menu] → Detailed setup → Signal condition → 
DP Setup →
→ Pres LRV Lower range value for differential 
pressure
→ Pres URV Upper range value for differential 
pressure
→ Pres Unit Unit for differential pressure
→ Pres Damp Damping time constant for differential 
pressure
Call up and setting of static pressure related 
parameters
[Root Menu] → Detailed setup → Signal condition → 
SP Setup →
→ SP LRV Lower range value for static pressure
→ SP URV Upper range value for static pressure
→ SP Unit Unit for static pressure
→ SP Damp Damping time constant for static 
pressure
Call up and setting of external temperature related 
parameters
[Root Menu] → Detailed setup → Signal condition → 
ET Setup →
→ ET LRV Lower range value for external 
temperature
→ ET URV Upper range value for external 
temperature
→ ET Unit Unit for external temperature
→ ET Damp Damping time constant for external 
temperature