Owner's manual
<5. Parameter Summary>
5-6
IM 01C25R02-01E
Function Label Item Contents Default value Handling *
1
Event
Notication
Latched Device
Status
HART 7
Device status when event occurred W
Latched Status
group 1 to 11
HART 7
Field device status when event
occured
W
Latched Ext dev
status
HART 7
Latched Device
Diagnostic Status 0
HART 7
Latched Device
Diagnostic Status 1
HART 7
Latched AO
saturated
HART 7
Latched AO xed
HART 7
Flow setup Flow Damp Damping time constant for ow 0.00 to 100.00 sec W
Flow LRV Lower range value for ow W
Flow URV Upper range value for ow W
Vol Flow Base Dens Volume Flow Base Density Value W
Flg temp Flg temp Calculated ange temperature
value
RG
Flg temp Coef Flg temp Coef 0 WG
Flg temp Lim Flg temp Hi Alarm
Val
Upper limit of Flange temperature
120 °C (deg C)
WG
Flg temp Lo Alarm
Val
Lower limit of Flange temperature -40 °C (deg C) WG
Fluct Variables fDP Average value of the sum of
squares of differential pressure/
pressure uctuations
RG
fDP Status Status of fDP RG
fSPl Average value of the sum of
squares of low-pressure-sidestatic
pressure uctuations
RG
fSPl Status Status of fSPl RG
fSPh Average value of the sum of
squares of high-pressure-side
static pressure uctuations
RG
fSPh Status Status of fSPh RG
Flg temp Flg temp Calculated ange temperature
value
RG
Keypad Input Change PV Assgn Change the allocation to PV M
PV Damp Damping time constant for PV W
PV is Current PV R
PV LRV Lower range value for PV W
PV URV Upper range value for PV W
Loop test Loop test Test output setting Within AO lower and upper
limits
M
Test Auto Release
Time
“Flow simulation”, “DO Test”
and “Test output” duration time
selection.
10min, 30min, 60min, 3h,
6h, 12h
10min W
Low cut Low cut Low cut 0.00 to 20.00% 10.00% W
Low cut mode Low cut mode Off or On Off W
*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)