Owner's manual

<5. Parameter Summary>
5-4
IM 01C25R02-01E
Function Label Item Contents Default value Handling *
1
Display setup Bar Indicator Bar indicator Off or On On W
Disp Out 1/Disp1 LCD output 1 PV %, Flow, Pres, SP, EXT.
TEMP, ENGR.PV, or TOTAL
FLOW
PV % W
Disp Out 2/Disp2 LCD output 2 PV %, Flow, Pres, SP, EXT.
TEMP, ENGR.PV, TOTAL
FLOW, or Not used
Not used W
Disp Out 3/Disp3 LCD output 3 (Ditto) Not used W
Disp Out 4/Disp4 LCD output 4 (Ditto) Not used W
Disp % Reso % display resolution Normal or High resolution Normal W
Engr exp User set exponent ---, x10, x100, x1000 --- or as
specied
W
Engr LRV User set lower range value Unit specied in Set Engr Unit As specied W
Engr point Decimal place for user set 0 to 4 2 W
Engr URV User set upper range value Unit specied in Set Engr Unit As specied W
ET disp point Decimal place for external
temperature
0 to 4 2 W
Flow disp point Decimal place for ow 0 to 4 2 W
Modify Engr Unit User set engineering unit M
Pres disp point Decimal place for differential
pressure
0 to 4 2 W
Set Engr Unit Engineering unit select M
SP disp point Decimal place for static pressure 0 to 4 2 W
TF disp point Decimal place for total ow 0 to 4 2 W
Squawk
HART 7
Squawk Specify the device under the
communication (turn the LCD
on).
M
DP setup Pres Damp Damping time constant for DP 0.00 to 100.00 sec W
Pres Min Span Minimum span for differential
pressure
R
Pres LRV Lower range value for differential
pressure
W
Pres LSL Lower sensor limit for differential
pressure
R
Pres URV Upper range value for differential
pressure
W
Pres USL Upper sensor limit for differential
pressure
0 to 4 R
Error log Error log Clear Clear error records M
Error log view Error records Log1 (latest) to log4 M
ET setup ET Damp Damping time constant for ET 0.00 to 100.00 sec W
ET Fixed External temperature x mode No,Yes, or FALL BACK No W
ET Min Span Minimum span for external
temperature
R
ET LRV Lower range value for ET W
ET LSL Lower sensor limit for ET R
ET URV Upper range value for ET W
ET USL Upper sensor limit for ET R
Fixed ET Val Temperature value at ET x mode 20 °C (deg C) W
*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)