Owner's manual
<5. Parameter Summary>
5-1
IM 01C25R02-01E
5. Parameter Summary
Function Label Item Contents Default value Handling *
1
Analog output AO alm typ Analog output alarm type High or Low R
AO lower limit Lower limit of analog output 3.8000 to 21.6000 mA 3.8000 mA W
AO upper limit Upper limit of analog output 3.8000 to 21.6000 mA 21.6000 mA W
Auto recover Auto-recover from hardware error Off or On On W
Analog output
trim
Clear D/A trim Reset analog output trim M
D/A trim Analog output trim with ammeter M
Scaled D/A trim Analog output trim with voltmeter M
Channel ags Analog channel ags 0x00 R
Burst mode Burst mode Burst mode *
2
Off or On
HART 5
Off or Wired HART Enabled
HART 7
Off W
Burst option
HART 5
Burst option Xmtr Variables, PV, % range/
current, Process vars/crnt
W
Burst Xmtr Vals
HART 5
Burst transmitter values M
Burst Command
HART 7
Burst Command *
2
Cmd 1: PV
Cmd 2: % range/current
Cmd 3: Dyn vars/current
Cmd 9: Device vars w/status
Cmd33: Device Variables
Cmd 48: Read Additional
Device Status.
Cmd 1: PV W
Burst Variable
Code
HART 7
Device Variable for the Burst
Message *
2
Max 8 slots. Flow W
Burst Msg Trigger
Mode
HART 7
Burst Trigger Mode Selection Code
*
2
(Continuous, Window, Rising,
Falling, On-change)
Continuous R
Set Burst Trigger
HART 7
Congure burst trigger Congure Burst Msg Trigger
Mode and Burst Trigger Level
M
Set Burst Period
HART 7
Congure burst period Congure Update Period and
Max Update Period
M
Burst Trigger Level
HART 7
Burst Trigger Level *
2
0.0 R
Update Period
HART 7
Update Period for Burst mode *
2
Update period for burst
message
Burst Message
1: 0.5sec
2: 60sec
3: 60sec
R
Max Update Period
HART 7
Max Update Period for Burst mode
*
2
Maximum update period for
burst message
60 min R
Date Date Date **/**/** W
Descriptor Descriptor Descriptor 16 alphanumerics W
*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)