<4. Diagnostics>
4-15
IM 01C25R02-01E
fDP is not enough.
No blockage can be detected if fDP is not larger
than the specied value.
Only fDP is enough.
“A Blocking” or “B Blockingcan be detected
if fSPl and fSPh are not larger than specied
values.
fDP and fSPl are enough.
“H Side Blocking” and “Large Fluct H” can not
be detected if fSPh is not larger than specied
value.
fDP and fSPh are enough.
“L Side Blocking” and “Large Fluct L” can not
be detected if fSPl is not larger than specied
value.
fDP, fSPl and fSPh are enough.
All alarm modes can be detected even if BlkF is
not within the specied values.
4.2.2.7 Obtain Reference Values
The pressure uctuation values are reduced
when the impulse line is plugged. Therefore, the
reference value is required to determine the degree
of reduction.
IMPORTANT
If the impulse line is about to be plugged at
the time when a reference value is obtained,
blockages cannot be detected accurately.
The impulse lines on both the high-pressure
and low-pressure sides need to be cleaned
before a reference value is obtained.
All air bubbles need to be adequately purged
before a reference value is obtained.
Reference values must be obtained under
operating condition.
Start of Sampling
The sampling of reference value is carried out for
180 sec, which is the default value set to Diag
Period.
1) Conrm that the sampling period (Diag Period)
is set to 180 sec.
2) Set “Referenceto Diag Mode.
The sampling starts soon after the setting.
IMPORTANT
For the each parameter, the one value is
given. If Reference is set to Diag Mode
again, the value is updated and overwritten.
If the power supply is shut down during the
sampling, Diag Mode becomes “Stop”. Set
“Reference” to Diag Mode in order to carry
out the sampling again.
End of Sampling
After about 180 sec, the sampling automatically
nishes. The “Reference setting of Diag Mode
moves automatically to “Calculation”.
Conrm that the setting of Diag Mode moves to
“Calculation”.
Reference Values
Conrm the latest values are obtained into the
following parameters.
Ref fDP
Ref fSPl
Ref fSPh
Ref BlkF
Ref DPAvg
Procedure to call up the display
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Diag/Service Diag
Parameters ILBD parameters
Status Diag Reference Ref fDP/
Ref fSPl/Ref fSPh/Ref BlkF/Ref DPAvg
DTM (HART 5) Diag and Service Advanced
Diag Conguration Impulse Line
Blockage Detection Ref fDP/Ref
fSPl/Ref fSPh/Ref BlkF/Ref DPAvg