Owner's manual

<3. Parameter Setting>
3-39
IM 01C25R02-01E
4) Applying the new protocol revision
a. Close the conguration tool
After completion of Chg universal rev
method, close the HART conguration tool.
NOTE
When using a FieldMate, close the main display
of FieldMate.
b. Restart the transmitter
Turn off the power to the transmitter, and turn
it on.
IMPORTANT
New protocol revision is applied only after having
performed restart of the transmitter.
NOTE
A new HART revision number is displayed on
the integral indicator for three (3) seconds after
restart the transmitter. (Refer to section 2.1)
5) Conrming the new protocol revision
a. Restart the HART conguration tool
NOTE
When execute the other parameter conrmation
or setting change, execute after restart the
conguration tool.
b. Conrm the new HART protocol revision
number
Call up the Universal rev parameter, and conrm
that the new HART revision number is displayed.
Procedure to call up the Universal rev.
parameter.
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Detailed setup
Device information Field
device info Revision #’s
Universal rev
DTM (HART 5) Conguration HART
Universal rev.
5 HART protocol revision: 5
7 HART protocol revision: 7