Owner's manual

<3. Parameter Setting>
3-36
IM 01C25R02-01E
e. Burst Mode
When the Burst mode is set to “Wired HART
Enabled”, the transmitter starts to send the data.
Procedure to call up the display
DD (HART 7)
DTM (HART 7)
[Root Menu] Detailed setup
Output condition
→HART output Burst condition
Burst Message 1,2 or 3
Burst mode Wired HART
Enabled
3.3.15.2.2 Event Notication
When a setting change and a change of the Self-
diagnostics occur, device detect it as an event and
can transmit an alarm signal continuously.
Up to four events that occurred can be stored.
When using this function, set to Burst mode as
“Wired HART Enabled”.
(1) Set Event Notication
Procedure to call up the display
DD (HART 7)
DTM (HART 7)
[Root Menu] Detailed setup
→Output condition →HART
output Burst condition
Event Notication
Event Mask Set the status to detect
Event
Notication
Retry Time
Set the retry time when the event
occur.
Max Update
Time
Set the retry time when the event
does not occur.
Event Debounce
Interval
The setting of the minimum event
duration
Event
Notication
Control
Stop the event monitor: Off
Shift to the monitor state: Enable
event notication on token-
passing data link layer
a) Event Mask
Set the status to detect in the Event Mask
parameter.
Device Status Mask
Status group 1 Mask to 11 Mask
Ext dev status Mask
Device Diagnostic Status 0 Mask
Device Diagnostic Status 1 Mask
AO saturated Mask
AO xed Mask
b) Event Notication Retry Time/ Max Update
Time/ Event Debounce Interval
Set to Event Notication Retry Time, Max Update
Time and Event Debounce Interval.
For Event Notication Retry Time, set the value
that is smaller than Max Update Time.
Event Notication
Retry Time
/Max Update Time
Event Debounce Interval
--- Off
0.5 s 0.5 s
1 s 1 s
2 s 2 s
4 s 4 s
8 s 8 s
16 s 16 s
32 s 32 s
1 min 1 min
5 min 5 min
10 min 10 min
15 min 15 min
30 min 30 min
45 min 45 min
60 min 60 min
c) Event Notication Control
Select “Enable event notication on token-passing
data link layerin the Event Notication Control
parameter to shift to the monitor state:
(2) Acknowledge Event Notication
The transmission of the event message stops when
event is approved.
Procedure to call up the display
DD (HART 7)
DTM (HART 7)
[Root Menu] Detailed
setup →Output condition
HART output Burst condition
Event Notication
Knowledge
Acknowledge
Event Notication
Acquisition of the event number
and approval.
a) Get Event Number
Conrm the latest event number.
Execute Acknowledge Event Notication
method.
1) Enter Event Number is set to “0”.
2) OK.
3) Set “Trans 0: Read Event Noticaiton” to
Select Transaction.
4) OK.
5) Conrm Event Number.