Owner's manual
<3. Parameter Setting>
3-33
IM 01C25R02-01E
Table 3.8 Burst parameters
Command parameter Burst Command
Burst Msg Trigger
Mode
Burst Trigger
Source
Burst Trigger Units
PV
(Either of differential
pressure, static pressure,
external temperature, ow
rate)
Cmd1:PV Continuous --- ---
Window PV Depend on the
assigned variable to
PV
Rising
Falling
On-change
% range/current
(Percent of range, Loop
current)
Cmd2:% range/current Continuous --- ---
Window % range %
Rising
Falling
On-change
Process vars/current
(Loop current, PV, SV, TV,
QV)
Cmd3:Dyn vars/current Continuous --- ---
Window PV Depend on the
assigned variable to
PV
Rising
Falling
On-change
Process vars/% range/
current with status
*1
(Select up to eight variables
from differential pressure,
static pressure, external
temperature, ow rate, total
ow, percent of range, loop
current, PV, SV, TV and
QV)
*2
Cmd9:Device vars w/Status Continuous --- ---
Window Top of Burst
Device Variables
Depends on mapping
Rising
Falling
On-change
Process vars/% range/
current
(Select up to four variables
from differential pressure,
static pressure, external
temperature, ow rate, total
ow, percent of range, loop
current, PV, SV, TV, and
QV)
*2
Cmd33:Device Variables Continuous Top of Burst
Device Variables
Depend on the
assigned variable to
Burst Device Variables
Window
Rising
Falling
On-change
Self diagnosis information Cmd48:Read
Additional Device Status
Continuous --- ---
On-change All status ---
*1 : Output the data with time and status.
*2 : Select at Burst Device Variables