Owner's manual

<3. Parameter Setting>
3-29
IM 01C25R02-01E
(5) Squawk (Effective only when setting to
HART 7)
This feature can be used to identify the
communicating transmitter by remotely causing
LCD to display the particular pattern as shown in
the Figure 3.3.
“SQUAWK” continues for approximately 15
seconds, then is released automatically.
Enter the larger number to “Change number of
squawks to makein order to prolong the duration
of squawk indication.
Procedure to call up the Squawk display
[Root Menu] Diag/Service Test Squawk
P
S P
T
F
F0309.ai
Figure 3.3 LCD display for Squawk
3.3.14 Basic Flow Calculation (Basic mode)
In the case of Basic mode, ow operation and
density compensation are performed conventionally
with the ow factors manually input.
The ow rate is calculated using the constant ow
factor.
Density is compensated as follows according to the
selection of gas or liquid.
Gas: Compensation as ideal gas by
temperature and pressure.
Liquid: Compensation by temperature.
There are an automatic compensation mode and
basic mode in the ow calculation, and either is
selected in the Flow Calc Mode parameter.
Procedure to call up the display
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Detailed setup
Basic Flow Calc Flow Calc Mode
DTM (HART 5) Conguration Basic Flow Calc
Flow Calc Mode
Display Item Contents
Basic Mode Basic calculation mode
Auto Comp.
Mode
Automatic compensation mode
(Use FSA120 for this mode)
Select “Basic Modehere, and set the parameters
according to the procedure of Table 3.2.
FSA120 (FieldMate FlowNavigator) can congure
both automatic compensation mode and basic
mode. For detail, refer to the User’s Manual of
FSA120 FieldMate FlowNavigator (IM 01C25R51-
01E).