Owner's manual

<3. Parameter Setting>
3-24
IM 01C25R02-01E
(1) Alarm Setting
Select the process variable at Process Alert which
the alarm is set, then set the alert mode for that
value.
Procedure to call up the display
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Detailed setup
Output condition Process Alerts
DTM (HART 5)
Conguration Process Alerts
Selection of
the process
variable for
alarm
Pres Alert Mode: Differential
pressure
SP Alert Mode: Static pressure
ET Alert Mode: External
temperature
Flow Alert Mode: Flow rate
Selection of
alert mode
Off: Disable the alert function
Hi Al Detect: High side alert detection
Lo Al Detect: Low side alert detection
Hi/Lo Al Detect: High and Low side
alert detection
(2) Threshold Level Setting
Set the threshold of high and low alert value for
alarm generation.
Procedure to call up the display
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Detailed setup
Output condition Process Alerts
DTM (HART 5) Conguration Process Alerts
Parameter Detail
Pres Hi Alert
Val
Set the threshold value of upper side
for differential pressure
Pres Lo Alert
Val
Set the threshold value of lower side
for differential pressure
SP Hi Alert
Val
Set the threshold value of upper side
for static pressure
SP Lo Alert
Val
Set the threshold value of lower side
for static pressure
ET Hi Alert
Val
Set the threshold value of upper side
for external temperature
ET Lo Alert
Val
Set the threshold value of lower side
for external temperature
Flow Hi Alert
Val
Set the threshold value of upper side
for ow rate
Flow Lo Alert
Val
Set the threshold value of lower side
for ow rate
3.3.12 Status Output and Pulse Output
EJX multivariable transmitter has a contact output.
Select the type of output, status output or pulse
output, and set the unit, value etc.
(1) Selecting of output signal
Status output or pulse output can be selected for
the contact output.
Procedure to call up the display
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Detailed setup
Output condition Process Alerts
DO cong DO Signal type
DTM (HART 5)
Conguration Process Alerts DO
Signal type
Status Output On When Al.
Detect
Output is “ON” when
alert is detected
Off When Al.
Detect
Output is “OFFwhen
alert is detected
Pulse Output Scaled Pulse Scaled pulse output
Frequency Frequency output
<Example>
Set the status output to output an off signal when
the input pressure exceeds 75 kPa with the alert
mode of Hi. Al Detect.
1) Select Off When Al. Detect
2) Select Pres Alert Mode: Differential pressure” (Refer
to subsection 3.3.11(1) Alarm Setting)
3) Select Hi Al Detect: High side alert detection(Refer
to subsection 3.3.11(1) Alarm Setting)
4) Enter “75kPato Pres Hi Alert Val (Refer to subsec-
tion 3.3.11(2) Threshold Level Setting)
CAUTION
Whenever turning on the transmitter or detecting
the short interruption, check if contact output
correctly reects the alarm status and test
the ON/OFF action of contact output by the
parameter DO test to conrm that the contact
output operates correctly.
(2) Setting of status output
This feature is used for a transistor output (open
collector) of an on/off signal according to the
status of high and low alarm limits, which are
user-congurable values as shown in subsection
3.3.11 Alarm. The status output can be assigned
as any combination of the high or low limits of
the input pressure, input static pressure, external
temperature, or ow.