Owner's manual

<3. Parameter Setting>
3-19
IM 01C25R02-01E
Procedure to call up the display
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Detailed setup
Display condition Engr disp range
Set Engr
Unit
Select the engineering unit
Engr LRV Lower range value
Engr URV Upper range value
Engr exp Exponents for user scale display
Engr point Decimal point position for user scale
display
Select the engineering unit from the list. Available
units are shown below
kPa
MPa
mbar
bar
psi
psia
mmH
2
O
mmHg
mmHgA
mmAq
mmWG
Torr
inH
2
O
inHg
inHgA
ftH
2
O
gf/cm
2
kgf/cm
2
kg/cm
2
G
kg/cm
2
A
atm
kg/h
t/h
m
3
/h
m
3
/min
l/h
l/min
kl/h
kl/min
Nl/h
Nl/min
Nm
3
/h
Nm
3
/min
ACFH
ACFM
CFH
SCFM
GPH
GPM
m
mm
in
ft
kg/m
3
g/cm
3
At Modify Engr Unit parameter, user can set your
own unit also.
Up to eight alphanumeric characters, spaces or one
slashe (/) can be input at Modify Engr Unit; only
the rst six are displayed on the integral indicator.
Procedure to call up the display
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Detailed setup
Display condition Engr disp range
Modify Engr
Unit
Set your own unit
Note that following symbols are not available:
# % & < > . * : + - , ( )
The integral indicator shows “-- -- -- -- -- --” when
these symbols or more than two slashes are
entered.
[For DTM (HART 5)]
User can input the desired unit at Engr Unit.
Procedure to call up the display
DTM (HART 5) Conguration →Local Display
Engr Unit Set the engineering unit
Engr LRV Lower range value
Engr URV Upper range value
Engr exp Exponents for user scale display
Engr point Decimal point position for user scale
display
Available characters and symbols for Engr Unit are
the same as for Modify Engr Unit shown above.
3.3.5 Total Flow Setup
(1) Mode setting
Set the parameters to start, stop, and reset the total
ow.
To start the total ow measurement by normal
mode, call up the Total Flow Mode display and set
the mode.
Procedure to call up the display
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Detailed setup
Signal condition Total Flow Total
Flow Mode
DTM (HART 5) Conguration Total Flow Total
Flow Mode
Reset Reset the total ow value
Start Start the total ow measurement.
Total value is limited at 9.99E29.
Stop Stop the total ow measurement
Start Cyclic Start the total ow measurement.
When the total ow value reaches
999999, the count restarts at 0.
(2) User unit conguration
You can set your own unit for total ow.
Select the Base Unit as an base unit, then set the
Cvt Val for the conversion coefcient with the user
unit.
Procedure to call up the display for DD
(HART 5/HART 7) and DTM (HART 7)
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Detailed setup
Signal condition Total Flow
Cong User Unit
Set Base
Unit
Select the Base Unit from the list
Modify Unit Set the special total ow unit
Cvt Val Enter the conversion value
Procedure to call up the display for DTM
(HART 5)
DTM (HART 5) Conguration Total Flow
Conf User Unit Set
Base Unit
Select the Base Unit from
the list
Conf User Unit
Modify Unit
Set the special total ow unit
Conf User Unit Cvt
Val
Enter the conversion value
Base Unit
g oz yd3
kg gal ft3
t L in3
lb Impgal Nm3
STon m3 NL
LTon bbl SCF