Procedure to call up the display using DD
(HART 5/HART 7) and DTM (HART 7)
PV related
parameter
[Root Menu] Process variables
Output vars PV
PV is Current PV value
Change PV
Assgn
Select the variable assigned to PV
(Flow, Pres, SP, ET)
SV related
parameter
[Root Menu] Process variables
Output vars SV
SV is Current SV value
Change SV
Assgn
Select the variable assigned to SV
(Flow, Pres, SP, ET, Total Flow)
TV related
parameter
[Root Menu] Process variables
Output vars TV
TV is Current TV value
Change TV
Assgn
Select the variable assigned to TV
(Flow, Pres, SP, ET, Total Flow)
4V/QV related
parameter
[Root Menu] Process variables
Output vars 4V/QV
4V is / QV is Current 4V/QV value
Change
4V Assgn
/Change QV
Assgn
Select the variable assigned to 4V/QV
(Flow, Pres, SP, ET, Total Flow)
Procedure to call up the display using DTM
(HART 5)
PV related item Conguration Output Variables
PV is Current PV value
Change PV
Assgn
Select the variable assigned to PV
(Flow, Pres, SP, ET)
It is similar about SV, TV and 4V.
The process variables that can be assigned are Flow,
Pres, SP, ET, and Total Flow.
3.2.3 Measuring Range
This section shows how to conrm and change
the parameters for measuring range of ow rate,
differential pressure, static pressure, external
temperature, and total ow, and also unit and
damping time constant.
These parameters are set at the factory before
shipment if specied at the time of order.
Follow the procedure below to change them.
About the differential pressure, static pressure and
external temperature, settable range are shown
on the parameters of LSL (Lower settable limit),
USL (Upper settable limit) and Min span (Minimum
span). Set the data within the range.
Procedure to call up the display
Call up and setting of ow related parameters
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Detailed setup
Signal condition Flow Setup
DTM (HART 5) Conguration Flow
Flow LRV Lower range value for ow
Flow URV Upper range value for ow
Flow Unit Unit for ow
Flow Damp Damping time constant for ow
Call up and setting of differential pressure related
parameters
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Detailed setup
Signal condition DP Setup (or Pres
Setup)
DTM (HART 5) Conguration Pressure Sensor
Pres LRV Lower range value for differential
pressure
Pres URV Upper range value for differential
pressure
Pres Unit Unit for differential pressure
Pres Damp Damping time constant for differential
pressure
Call up and setting of static pressure related
parameters
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Detailed setup
Signal condition SP Setup
DTM (HART 5) Conguration Static Pressure
Sensor
SP LRV Lower range value for static pressure
SP URV Upper range value for static pressure
SP Unit Unit for static pressure
SP Damp Damping time constant for static
pressure
Call up and setting of external temperature related
parameters
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Detailed setup
Signal condition ET Setup
DTM (HART 5) Conguration External
Temperature Sensor
ET LRV Lower range value for external
temperature
ET URV Upper range value for external
temperature
ET Unit Unit for external temperature
ET Damp Damping time constant for external
temperature
Call up and setting of total ow related parameters
DD (HART 5/7)
DTM (HART 7)
[Root Menu] Detailed setup
Signal condition Total Flow
DTM (HART 5) Conguration Total Flow
Total Flow
Unit
Unit for total ow