<10. General Specications>
10-2
IM 01C25R01-01E
Output specications for HART Protocol Type “◊
Output
Dual output (Both analog and pulse/contact
output can be obtained simultaneously).
In this case refer to the item “Wiring example for
analog output and status/pulse output”.
HART Protocol Revision
HART protocol revision can be selected from 5
or 7 when ordering.
The protocol revision can be changed by user
conguration.
Note: Protocol revision supported by HART
conguration tool must be the same or higher
than that of the EJX multivariable transmitter.
Protocol revision supprted
by HART conguration tool
5 7
Protocol revision of
EJX multivariable
transmitter.
5
7
Í
: Communication OK
Í: Communication NG
Analog Output
Two wire 4 to 20 mA DC output, user-selectable
for Differential Pressure, Static Pressure,
External Temperature or Flow Rate signal.
Failure Alarm
Analog output status at CPU failure and
hardware error
Up-scale: 110%, 21.6 mA DC or more
(standard)
Down-scale: –2.5%, 3.6 mA DC or less
Analog output status at process abnormality
(Option code /DG6);
The result of process abnormality detected
by the advanced diagnostic function can
be reected to an analog alert status. The
following three setting modes are available.
Mode
Burnout Fall back Off
Standard 110%, 21.6mA or more
Holds to a
specied
value withun
the output
range from
3.8mA to
21.6mA
Normal
output
Option
Code
/C1 -1.25%, 3.8mA or less
/C2 -1.25%, 3.8mA or less
/C3 103.1%, 20.5mA or more
Pulse/Contact Output
Pulse or status output is selected by parameter
setting.
Transistor contact output (sink type).
Contact rating:
10.5 to 30 V DC, 120 mA DC max.
Low level: 0 to 2 V DC. (See gure below for
high and low levels (pulse output).)
HIGH level
LOW level
0 to 2 V
0V
F1001.ai
Pulse Output
Scaled pulse or frequency pulse output is
selected by parameter setting.
Scaled Pulse Output Function
Pulse is output by the unit of the scaled ow rate.
Scaled pulse can be totalized.
Frequency Output Function
Number of pulses output per second at 100% of
output.
Pulse frequency: Max. 10 kHz
Duty cycles: Approx. 50% (1:2 to 2:1)
Contact Output Function
High or low alarm
Status signal output mode can be reversed
(ON/OFF).
Signal Output (for HART protocol type)
Output
Flow
rate*
1
Differential
pressure
Static
pressure
External
temperature
Total
ow*
1
4-20mA
*
3
*
2
Pulse output
High/Low
alarm
*1: When Measurement Function Code B is specied.
*2: Square root output is not available. Low cut linear
mode is not supported.
*3: Reversed output is not available.