Output specications for HART Protocol Type “◊”
Output
Dual output (Both analog and pulse/contact 
output can be obtained simultaneously).
In this case refer to the item “Wiring example for 
analog output and status/pulse output”.
HART Protocol Revision
HART protocol revision can be selected from 5 
or 7 when ordering.
The protocol revision can be changed by user 
conguration.
Note: Protocol revision supported by HART 
conguration tool must be the same or higher 
than that of the EJX multivariable transmitter.
Protocol revision supprted 
by HART conguration tool
5 7
Protocol revision of 
EJX multivariable 
transmitter.
5
 
7
Í 
  : Communication OK
Í: Communication NG
Analog Output
Two wire 4 to 20 mA DC output, user-selectable 
for Differential Pressure, Static Pressure, 
External Temperature or Flow Rate signal.
Failure Alarm
•  Analog output status at CPU failure and 
hardware error
Up-scale: 110%, 21.6 mA DC or more 
(standard)
Down-scale: –2.5%, 3.6 mA DC or less
•  Analog output status at process abnormality 
(Option code /DG6);
The result of process abnormality detected 
by the advanced diagnostic function can 
be reected to an analog alert status. The 
following three setting modes are available.
Mode
Burnout Fall back Off
Standard 110%, 21.6mA or more
Holds to a 
specied 
value withun 
the output 
range from 
3.8mA to 
21.6mA
Normal 
output
Option
Code
/C1 -1.25%, 3.8mA or less
/C2 -1.25%, 3.8mA or less
/C3 103.1%, 20.5mA or more
Pulse/Contact Output
Pulse or status output is selected by parameter 
setting.
Transistor contact output (sink type).
Contact rating: 
10.5 to 30 V DC, 120 mA DC max.
Low level: 0 to 2 V DC. (See gure below for 
high and low levels (pulse output).)
HIGH level
LOW level
0 to 2 V
0V
F1001.ai
Pulse Output
Scaled pulse or frequency pulse output is 
selected by parameter setting.
Scaled Pulse Output Function
Pulse is output by the unit of the scaled ow rate.
Scaled pulse can be totalized.
Frequency Output Function
Number of pulses output per second at 100% of 
output.
Pulse frequency: Max. 10 kHz
Duty cycles: Approx. 50% (1:2 to 2:1)
Contact Output Function
High or low alarm
Status signal output mode can be reversed 
(ON/OFF).
Signal Output (for HART protocol type)
Output
Flow 
rate*
1
Differential
pressure
Static
pressure
External
temperature
Total 
ow*
1
4-20mA
*
3
*
2
 
Pulse output
 
High/Low 
alarm
   
*1:  When Measurement Function Code B is specied.
*2:  Square root output is not available. Low cut linear 
mode is not supported.
*3:  Reversed output is not available.