    <9.  Maintenance>
9-12
IM 01C25R01-01E
Integral 
indicator  
HART communicator 
display  
Cause
4-20mA Output  
operation during error  
Countermeasure  
Status 
group  
AL.87
FLG. HI
FT high alarm Flange temperature 
exceeds a preset upper 
limit.
It depends on the Diag Out 
Option setting.
Off: Continue to operate 
and output.
Burnout:Outputs AO 
upper limit or AO lower 
limit.
Fall back:Outputs Diag 
Out Fixed Val.
Check the heater 
failure.
Check the capsule 
temp. and Amplier 
temp.
Adjust Flg Temp 
Coef.
9
AL.87
FLG. LO 
FT low alarm Flange temperature is 
below a preset lower 
limit.
AL.88
INVR.DP 
Invalid Ref DP
Differential pressure/
pressure uctuation 
does not reach the 
reference level required 
to blockage detection 
so that no blockage 
detection is carried out.
Continue to operate and 
output.
Check process 
condition.
AL.88
INVR.SL 
Invalid Ref SPL Low-pressure-side 
uctuation does not 
reach the reference 
uctuation level required 
to blockage detection.
AL.88
INVR.SH 
Invalid Ref SPH
High-
pressure-side
uctuation does not reach 
the reference uctuation 
level required to blockage 
detection.
AL.88
INVR.F 
Invalid Ref F BlkF can not be used for 
blockage detection for 
some reasons.
AL.89
ILBD.OV 
ILBD over range Appointed the diagnosis 
range outside.
Check process 
condition.
AL.89
B BLK 
B Blocking B Blocking (both-side 
blockage) is detected.
It depends on the Diag Out 
Option setting.
Off: Continue to operate 
and output.
Burnout: Outputs AO 
upper limit or AO lower 
limit.
Fall back: Outputs Diag 
Out Fixed Val.
Check process 
condition.
10
AL.89
H BLK 
H Side Blocking High-pressure-side 
blockage is detected.
AL.89
L BLK 
L Side Blocking Low-pressure-side 
blockage is detected.
AL.89
H LRG 
Large Fluct H Pressure uctuation 
amplitude of high-
pressure side is large.
AL.89
L LRG 
Large Fluct L Pressure uctuation 
amplitude of low-
pressure side is large.
AL.89
A BLK 
A Blocking A Blocking (single-side 
blockage) is detected.
AL. 90  
SIM  
Simulate Mode   Under Simulation Mode.   Simulate input output.   Check Simulation 
Mode.  
5  
—
ET Fixed Mode   Under Temperature Fix 
Mode. PV is ET  
Temp. Output Fix at 4mA.   Leave from 
Temperature Fix 
Mode.  
7  