    <8.  Operation>
8-2
IM 01C25R01-01E
■  Conrming that Transmitter is Operating 
Properly
Using the HART communicator
•  If the wiring system is faulty, ‘No device found at  
adress O Poll' or communication error’ appears 
on the display.
•  If the transmitter is faulty, ‘error message’ 
appears on the display.
Using the integral indicator
•  If the wiring system is faulty, the display stays 
blank.
•  If the transmitter is faulty, an error code is 
displayed.
Self-diagnostic error on the integral indicator
(Faulty transmitter)
F0802.ai
Figure 8.2  Integral Indicator with Error Code
NOTE
If any of the above errors are indicated on 
the display of the integral indicator or the 
communicator, refer to subsection 9.5.2 for the 
corrective action.
 ■  Verify and Change Transmitter Parameter 
Setting and Values
The parameters related to the following items are 
set at factory as specied in order.
•  Calibration range
•  Software damping (optional)
Other parameters like following are shipped with the 
default setting.
•  Low-cut
•  Process alarm setting
•  Write protection 
To conrm or change the values, see  
IM 01C25R02-01E or 01C25R03-01E.
8.2  Zero Point Adjustment
After completing preparations for operating the 
transmitter, adjust the zero point.
Zero point adjustment can be done by turning the 
transmitter’s zero-adjustment screw or by using 
the communicator. This section describes the 
procedure for the zero-adjustment screw. For the 
communicator procedure, see the communication 
manual.
IMPORTANT
Do not turn off the power to the transmitter 
immediately after performing a zero point 
adjustment. Powering off within 30 seconds of 
performing this procedure will return the zero 
point to its previous setting.
NOTE
Before performing this adjustment, make sure 
that the external zero adjustment function has 
been enabled by a parameter setting. 
External zero adjustment function only to the 
differencial pressure signal.
To check the output signal, use a digital multimeter, 
calibrator, or communicator.
8.2.1  Adjusting Zero Point for Differential 
Pressure
Before adjusting zero point, make sure that the 
equalizing valve is open.
F0803.ai
Zero-adjustment
screw cover
Figure 8.3  External Zero Adjustment Screw