Manual
    <7.  Wiring>
7-4
IM 01C25R01-01E
7.5.2  Wiring Installation
(1)  General-use Type and Intrinsically Safe 
Type
With the cable wiring, use a metallic conduit or 
waterproof glands.
•  Apply a non-hardening sealant to the terminal 
box connection port and to the threads on the 
exible metal conduit for waterproong.
F0710.ai
Flexible metal conduit
Wiring metal
conduit
Tee
Drain plug
Apply a non-hardening
sealant to the threads 
for waterproofing.
Figure 7.8  Typical Wiring Using Flexible Metal 
Conduit
(2)  Flameproof Type
Wire cables through a ameproof packing adapter, 
or use a ameproof metal conduit. 
■ Wiring cable through ameproof packing adapter.
•  Apply a non-hardening sealant to the terminal 
box connection port and to the threads on the 
ameproof packing adapter for waterproong.
Flameproof packing adapter
Flexible metal conduit
Wiring metal
conduit
Tee
Drain plug
Apply a non-hardening
sealant to the threads 
for waterproofing.
F0711.ai
Figure 7.9  Typical Cable Wiring Using Flameproof 
Packing Adapter
■ Flameproof metal conduit wiring
•  A seal tting must be installed near the terminal 
box connection port for a sealed construction.
•  Apply a non-hardening sealant to the threads of 
the terminal box connection port, exible metal 
conduit and seal tting for waterproong.
F0712.ai
Non-hazardous area
Hazardous area
Flameproof
heavy-gauge
steel conduit
Tee
Drain plug
Seal fitting
Gas sealing device
Flameproof flexible
metal conduit
Apply a non-hardening
sealant to the threads 
of these fittings for
waterproofing
After wiring, impregnate the fitting
with a compound to seal tubing.
Figure 7.10  Typical Wiring Using Flameproof Metal 
Conduit
7.6  RTD Cable Connection 
Connection of the RTD cable is always required 
to measure external temperature. Follow the 
procedures below to connect and disconnect a 
cable when a cable gland or a conduit is used.
7.6.1  Connecting Shielded Cable with 
Cable Gland  
(External temperature input code: 
 -1, -2, -3, and -4)
•  RTD connection components: EJX multivariable 
transmitter, two cable glands, and RTD cable 
Two cable glands are attached.
YLPPUS
ESLUP
K
C
E
H
C
MRALA
Transmitter
Cable gland
Electrical connection
RTD cable 
with connector
Detail of connector
F0713.ai