Manual
    <7.  Wiring>
7-1
IM 01C25R01-01E
7.  Wiring
7.1  Wiring Precautions
IMPORTANT
•  The information in the sections from 7.2 
throught 7.5 (except for 7.5.2) is specic to 
HART protocol type. Refer to IM01C25R03-
01E for FOUNDATION Fieldbus protocol 
type or IM 01C25R05-01EN for Modbus 
Communication Type. 
•  Lay wiring as far as possible from electrical 
noise sources such as large capacity 
transformers, motors, and power supplies.
•  Remove the electrical connection dust cap 
before wiring.
•  All threaded parts must be treated with 
waterproong sealant. (A non-hardening 
silicone group sealant is recommended.)
•  To prevent noise pickup, do not pass signal 
and power cables through the same ducts.
•  Explosion-protected instruments must 
be wired in accordance with specic 
requirements (and, in certain countries, 
legal regulations) in order to preserve the 
effectiveness of their explosion-protected 
features.
•  The terminal box cover is locked by an 
Allen head bolt (a shrouding bolt) on ATEX 
ameproof type transmitters. When the 
shrouding bolt is driven clockwise using 
an Allen wrench, it goes in. The cover lock 
can then be released and the cover can 
be opened by hand. See subsection 8.4 
“Disassembly and Reassembly” for details.
•  Plug and seal an unused conduit connection.
•  Do not turn on power until all wirings 
including RTD nished.
7.2  Selecting the Wiring 
Materials
(a)  Use stranded leadwires or cables which are 
the same as or better than 600 V grade PVC 
insulated wire or its equivalent.
(b)  Use shielded wires in areas that are susceptible 
to electrical noise.
(c) In areas with higher or lower ambient 
temperatures, use appropriate wires or cables.
(d)  In environment where oils, solvents, corrosive 
gases or liquids may be present, use wires or 
cables that are resistant to such substances.
(e)  It is recommended that crimp-on solderless 
terminal lugs (for 4 mm screws) with insulating 
sleeves be used for leadwire ends.
7.3  Types of Output
Table 7.2 shows the wiring example according to 
the output types.
(1)  Analog Output (4 to 20 mA DC)
This instruments uses the same two wires for both, 
the signal and power supply. A DC power supply is  
required in a transmission loop. The total leadwire  
resistance including the instrument load and power  
distributor (supplied by the user) must conform to 
a  value in the permissible load resistance range. 
Refer to  Figure below.
F0701.ai
    E-10.5
    0.0244
(Ω)
Power supply voltage E (V DC)
600
250
R
10.5 16.6
25.2 42
External
load
resistance
Digital
Communication
range
R=
Figure 7.1  Relation between Power Supply 
Voltage and Load Resistance (4 to 20 
mA DC Output) 










