Manual
    <6.  Installing Impulse Piping>
6-3
IM 01C25R01-01E
(2)  Position of Process Pressure Taps and 
Transmitter
If condensate (or gas) accumulates in the impulse 
piping, it should be removed periodically by 
opening the drain (or vent) plugs. However, this will 
generate a transient disturbance in the pressure 
measurement, and therefore it is necessary to 
position the taps and route the impulse piping so 
that any extraneous liquid or gas generated in the 
leadlines returns naturally to the process piping. 
•  If the process uid is a gas, then as a rule the 
transmitter must be located higher than the 
process pressure taps.
•  If the process uid is a liquid or steam, then as a 
rule the transmitter must be located lower than 
the process pressure taps. 
(3) Impulse Piping Slope
The impulse piping must be routed with only an 
upward or downward slope. Even for horizontal 
routing, the impulse piping should have a slope of 
at least 1/10 to prevent condensate (or gases) from 
accumulating in the pipes.
(4)  Temperature Difference Between Impulse 
Lines 
If there is a temperature difference between the 
high and low impulse lines, the density difference 
of the uids in the two lines will cause an error in 
the measurement pressure. When measuring ow, 
impulse lines must be routed together so that there 
is no temperature difference between them.
(5)  Condensate Pots for Steam Flow 
Measurement
If the liquid in the impulse piping repeatedly 
condenses or vaporizes as a result of changes 
in the ambient or process temperature, this will 
cause a difference in the uid head between the 
high pressure and low pressure sides. To prevent 
measurement errors due to these head differences, 
condensate pots are used when measuring steam 
ow.
(6)  Preventing Wind Speed Effects in Very Low 
Differential Pressure Measurement
IMPORTANT
When using a differential pressure transmitter 
to measure very low pressures (draft pressure), 
the low pressure connection port is left open 
to atmospheric pressure (the reference 
pressure). Any wind around the differential 
pressure transmitter will therefore cause errors 
in the measurement. To prevent this, it will be 
necessary either to enclose the transmitter in 
a box, or to connect an impulse line to the low 
pressure side and insert its end into a wind-
excluding pot (cylindrical with a base plate).
(7)  Preventing Freezing
If there is any risk that the process uid in the 
impulse piping or transmitter could freeze, use a 
steam jacket or heater to maintain the temperature 
of the uid.
NOTE
After completing the connections, close the 
valves on the process pressure taps (main 
valves), the valves at the transmitter (stop 
valves), and the impulse piping drain valves, 
so that condensate, sediment, dust and other 
extraneous material cannot enter the impulse 
piping.










