    <3.  Handling Cautions>
3-10
IM 01C25R01-01E
MODEL: Specied model code.
STYLE: Style code
SUFFIX: Specied sufx code.
SUPPLY:  Supply voltage (HART 
Communication Type) 
Supply voltage and Power (Modbus 
Communication Type) 
For FOUNDATION Fieldbus 
communication type, refer to IM 
01C25R03-01E.
OUTPUT: Output signal. 
MWP: Maximum working pressure. 
CAL RNG: Specied calibration range. 
NO.: Serial number and year of production*
1
.
TOKYO  180-8750 JAPAN: 
The manufacturer name and the address*
2
.
  *1: The rst number in the second block of “NO.” column 
is the last one number of the production year.    
 second block
  NO. 91K819857      1
32     7 
  The year 2011
  *2: “180-8750” is a zip code which represents the 
following address. 
    2-9-32 Nakacho, Musashino-shi, Tokyo Japan  
  *3: The identication number of Notied Body.
3.9.4  IECEx Certication
a.  IECEx Flameproof Type
Caution for IECEx ameproof type.
Note 1. EJX multivariable transmitter with optional 
code /SF2 are applicable for use in 
hazardous locations:
•  No. IECEx CSA 07.0008
•  Applicable Standard: IEC60079-0:2004,  
IEC60079-1:2003
•  Flameproof for Zone 1, Ex d IIC T6...T4
•  Enclosure: IP66 and IP67
•  Maximum Process Temperature:  
120°C (T4), 100°C (T5), 85°C (T6)
•  Ambient Temperature: –50 to 75°C (T4),  
–50 to 80°C (T5), –50 to 75°C (T6)
•  Supply Voltage: 42 V dc max.
•  Output Signal: 4 to 20 mA dc
Note 2. Wiring
•  In hazardous locations, the cable entry 
devices shall be of a certied ameproof 
type, suitable for the conditions of use and 
correctly installed. 
•  Unused apertures shall be closed with 
suitable ameproof certied blanking 
elements. 
Note 3. Operation
•  WARNING: 
  AFTER DE-ENERGIZING, DELAY 5 
MINUTES BEFORE OPENING. 
•  WARNING:
  WHEN AMBIENT TEMPERATURE ≥ 65°C, 
USE THE HEAT-RESISTING CABLES ≥ 
90°C.
•  Take care not to generate mechanical 
sparking when accessing to the instrument 
and peripheral devices in a hazardous 
location.
Note 4. Maintenance and Repair
•  The instrument modication or parts 
replacement by other than authorized 
representative of Yokogawa Electric 
Corporation is prohibited and will void IECEx 
Certication.
3.10  EMC Conformity Standards
EN61326-1 Class A, Table 2 (For use in industrial 
locations)
EN61326-2-3 
CAUTION
•  This instrument is a Class A product, 
and it is designed for use in the industrial 
environment. Please use this instrument in 
the industrial environment only.
•  To meet EMC regulations, Yokogawa 
recommends that customers run signal 
wiring through metal conduits or use 
shielded twisted-pair cabling when installing 
EJX series transmitters in a plant.