Manual

<3. Handling Cautions>
3-10
IM 01C25R01-01E
MODEL: Specied model code.
STYLE: Style code
SUFFIX: Specied sufx code.
SUPPLY: Supply voltage (HART
Communication Type)
Supply voltage and Power (Modbus
Communication Type)
For FOUNDATION Fieldbus
communication type, refer to IM
01C25R03-01E.
OUTPUT: Output signal.
MWP: Maximum working pressure.
CAL RNG: Specied calibration range.
NO.: Serial number and year of production*
1
.
TOKYO 180-8750 JAPAN:
The manufacturer name and the address*
2
.
*1: The rst number in the second block of “NO.column
is the last one number of the production year.
second block
NO. 91K819857 1
32 7
The year 2011
*2: “180-8750is a zip code which represents the
following address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
*3: The identication number of Notied Body.
3.9.4 IECEx Certication
a. IECEx Flameproof Type
Caution for IECEx ameproof type.
Note 1. EJX multivariable transmitter with optional
code /SF2 are applicable for use in
hazardous locations:
No. IECEx CSA 07.0008
Applicable Standard: IEC60079-0:2004,
IEC60079-1:2003
Flameproof for Zone 1, Ex d IIC T6...T4
Enclosure: IP66 and IP67
Maximum Process Temperature:
12C (T4), 100°C (T5), 85°C (T6)
Ambient Temperature: –50 to 75°C (T4),
–50 to 80°C (T5), –50 to 75°C (T6)
Supply Voltage: 42 V dc max.
Output Signal: 4 to 20 mA dc
Note 2. Wiring
In hazardous locations, the cable entry
devices shall be of a certied ameproof
type, suitable for the conditions of use and
correctly installed.
Unused apertures shall be closed with
suitable ameproof certied blanking
elements.
Note 3. Operation
WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
WARNING:
WHEN AMBIENT TEMPERATURE 65°C,
USE THE HEAT-RESISTING CABLES
90°C.
Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
location.
Note 4. Maintenance and Repair
The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void IECEx
Certication.
3.10 EMC Conformity Standards
EN61326-1 Class A, Table 2 (For use in industrial
locations)
EN61326-2-3
CAUTION
This instrument is a Class A product,
and it is designed for use in the industrial
environment. Please use this instrument in
the industrial environment only.
To meet EMC regulations, Yokogawa
recommends that customers run signal
wiring through metal conduits or use
shielded twisted-pair cabling when installing
EJX series transmitters in a plant.