    <3.  Handling Cautions>
3-7
IM 01C25R01-01E
•  Ambient Temperature for gas-proof:  
–50 to 60°C
•  Process Temperature (Tp.): 120°C max.
•  Maximum Surface Temperature for dust-
proof:
  T85°C (Tamb.: –40* to 60°C, Tp.: 80°C)
  T100°C (Tamb.: –40* to 60°C, Tp.: 100°C)
  T120°C (Tamb.: –40* to 60°C, Tp.: 120°C)
    * –15°C when /HE is specied.
•  Enclosure: IP66 and IP67 
Note 2. Electrical Data
[Supply/Output circuit (terminals + and -)]
  In type of explosion protection intrinsic safety 
EEx ia IIC, only for connection to a certied 
intrinsically safe circuit with following maximum 
values:
  Ui = 30 V 
Ii = 200 mA 
Pi = 0.9 W 
Ci = 10 nF 
Li = 0 mH
[Pulse Output circuit (terminals - and pulse)]
  In type of explosion protection intrinsic safety 
EEx ia IIC, only for connection to a certied 
intrinsically safe circuit with following maximum 
values:
  Ui = 30 V 
Ii = 200 mA 
Pi = 0.9 W 
Ci = 10 nF 
Li = 0 mH
[External temperature input circuit (connector)]
  In type of explosion protection intrinsic safety 
EEx ia IIC, with following maximum values:
  Uo = 30 V 
Io = 95.4 mA 
Po= 468 mW 
Co = 11 nF 
Lo= 3.9 mH
Note 3. Installation
•  All wiring shall comply with local installation 
requirements. (Refer to the installation 
diagram)
•  When the analog and pulse circuits are 
connected to separate barriers, it shall be 
assured that the voltage difference between 
these output circuits is not more than 30 V.
•  When used in a potentially explosive 
atmosphere, Requiring the use of apparatus 
of equipment category 1D or 2D, certied 
cable entry devices shall be used that are 
suitable for the application and correctly 
installed.
Note 4. Maintenance and Repair
•  The instrument modication or parts 
replacement by other than authorized 
representative of Yokogawa Electric 
Corporation is prohibited and will void KEMA 
Intrinsically safe Certication.
Note 5. Special Conditions for Safe Use
•  In the case where the enclosure of the 
Pressure Transmitter is made of aluminium, 
if it is mounted in an area where the use of 
category 1 G apparatus is required, it must 
be installed such, that, even in the event of 
rare incidents, ignition sources due to impact 
and friction sparks are excluded.
Transmitter
Supply
Safety Barrier
Nonhazardous Location
[Installation Diagram]
Hazardous Location
+ 
– 
+ 
– 
F0305.ai
(*1)
Note 1
Sensor out
RTD sensor 
Note 2
 Without pulse output 
 With pulse output 
Transmitter
Supply
Safety Barrier
Nonhazardous Location
Hazardous Location
+ 
– 
+ 
– 
+
(*1)
Note 1
Sensor out
RTD sensor 
Note 2
Safety Barrier
+ 
– 
(*1)
Note 1
Pulse
Note 1:
  •  In any safety barriers used the output current must be 
limited by a resistor “R” such that Io=Uz/R.
  •  The safety barrier shall be certied by notify body EU 
as ATEX.
  •  When using non isolation barrier, connect (*1) to IS 
earthing system.
Note 2:
  •  RTD sensor is prepared by the user.
  •  The sensor signal line must withstand a test voltage of 
500 V AC.