<3. Handling Cautions>
3-5
IM 01C25R01-01E
[For CSA C22.2]
Explosion-proof for Class I, Groups B, C and
D.
Dustignition-proof for Class II/III, Groups E, F
and G.
Enclosure: TYPE 4X
Temperature Code: T6...T4
[For CSA E60079]
Flameproof for Zone 1, Ex d IIC T6...T4
Enclosure: IP66 and IP67
Maximum Process Temperature:
12C (T4), 100°C (T5), 85°C (T6)
Ambient Temperature: –50* to 75°C (T4),
–50* to 80°C (T5), –50* to 75°C (T6)
* –15°C when /HE is specied.
Power Supply:
42 V dc max. (HART Communication Type)
9 to 30 V dc, 250 mW (Modbus
Communication Type)
For FOUNDATION Fieldbus communication
type, refer to IM 01C25R03-01E.
Output signal:
4 to 20 mA (HART Communication Type)
Modbus (Modbus Communication Type)
For FOUNDATION Fieldbus communication
type, refer to IM 01C25R03-01E.
Note 2. Wiring
All wiring shall comply with Canadian
Electrical Code Part I and Local Electrical
Codes.
In hazardous location, wiring shall be in
conduit as shown in the gure.
WARNING:
A SEAL SHALL BE INSTALLED WITHIN
50cm OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTALLÉ À
MOINS DE 50cm DU BOÎTIER.
WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL
NOT REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2,
AUCUN JOINT N'EST REQUIS.
Note 3. Operation
WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
APS POWER-OFF, ATTENDRE 5
MINUTES AVANT D'OUVRIR.
WARNING:
WHEN AMBIENT TEMPERATURE 65°C,
USE THE HEAT-RESISTING CABLES
90°C.
QUAND LA TEMPÉRATURE AMBIANTE
65°C, UTILISEZ DES CÂBLES
SISTANTES Á LA CHALEUR 90°C.
Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
location.
Note 4. Maintenance and Repair
The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation and Yokogawa Corporation of
America is prohibited and will void Canadian
Standards Explosionproof Certication.
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Non-Hazardous
Locations
Hazardous Locations Division 1
Non-Hazardous
Locations
Hazardous Locations Division 2
50 cm Max.
Sealing Fitting
Conduit
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Sealing Fitting
F0304.ai
SUPPLY
PULSE
CHECK
ALARM
SUPPLY
PULSE
CHECK
ALARM
EJX910A
EJX910A