Example: Kfactor Calculation
Table 2.9 Flow Condition Example
Symbol Value Description
Qm 3011.76 (lb/h)
∆p 201.0935 inH2O@68degF Differential pressure
Tb 273.15 K Reference temperature unit: K
SPb 101.325 kPa abs Reference static pressure unit: kPa abs
T 293.15 K Temperature unit: K
SP 500 kPa abs Static pressure unit: kPa abs
Kfactor = Qm(lb/h) / ∆p × (Tb / T) × (SP / SPb)
= 3011.76 / 201.0935 × (273.15 / 293.15) × (500 / 101.325)
= 99.0464
Table 2.10 For HART Communicator (Function : Basic Flow Calc)
Symbol HART Parameter name Item
Kfactor Flow Calc Fixed
Calcuration xation value of ow
SPb Ref SP
Reference static pressure
Tb Ref Temp Reference pressure
TempK1 Temp K1
The rst in temperature correction coefcient for liquid
For volume ow: set 0.