Manual
    <2.  About the EJX Multivariable Transmitter>
2-6
IM 01C25R01-01E
2.5.1  Conguration Procedure for Basic 
Mode
Either a communicator or the mass ow 
conguration software is required to carry out 
conguration in basic mode.
Calculation of the basic mode parameters is 
necessary to perform conguration. Following 
shows the procedures for HART protocol type.
(1)  Have ready a power supply, a personal 
computer, a HART modem and the FSA120 
EJX-MV Conguration DTM.
(2)  Install the ow conguration software on the 
personal computer.  
This is not necessary if only the HART 
communicator is used for conguration.
(3) Connect the EJX multivariable transmitter to the 
power supply.
NOTE
Even when the RTD is not connected and alarm 
number 03 is displayed on the indicator, setting 
can be performed.
(4)  Connect the HART communicator or the HART 
modem to the transmitter.
(5)  Perform ow conguration. 
(6)  Execute ow simulation with the HART HHT 
or the FSA120 software in order to conrm the 
congured ow parameters. 
When the simulation is carried out, it is 
necessary to connect the RTD or mock 
resistance (about 100Ω) to the transmitter. 
Input the differential pressure, static pressure, 
and temperature values and then conrm that 
the desired ow has been obtained.
(7)  Remove the HART communicator or the HART 
modem from the transmitter.
(8)  Turn off the power supply.
NOTE
(1)  Refer to the following instruction manuals for 
more detailed explanation.
Setting with the HART HHT:  
IM01C25R02-01E.
Setting with the Fieldbus conguration tool: 
IM01C25R03-01E.
Setting with the FSA120: IM01C51R01-01E.
(2)  For the ow conguration in the eld after 
installation, perform only steps 4 to 7.
2.5.2  Calculation of the Basic mode 
parameters
There are two methods for the calculation of the 
Basic mode parameters.
Method 1: Calculating the Kfactor by ow 
parameters
Method 2: Calculating the Kfactor by means of the 
ow condition
Method 1. Calculating the Kfactor by ow 
parameters.
(1)  Selection of the ow equation
  Select the desired operational expression 
according to the uid type and the ow unit 
category shown in Table 2.1. 
(2)  Conrming the unit
  The unit to be used in this calculation is as 
follows:
  Differential pressure: Pa
  Static Pressure: kPa abs 
  Temperature: K
  The dimension of the pressure unit Pa are 
M•L
-1
•S
-2
  Where M: mass (Kg)
    L: Length (m)
    S: Time (second)
(3)  Preparation of ow parameters for Kfactor 
calculation
  Each parameter must be expressed in the 
following units.
d: m,
ρb and ρnorm: Kg/m
3
C, β, ε and K has no dimensions
(4)  Calculation of the unit conversion coefcient Nc 
The ow rate value does not change 
automatically when a ow unit parameter is set 
for the transmitter, and is always output as Kg/s 
(mass ow). M
3
/s (volume ow), Nm
3
/s (Normal 
volume ow.) 
In order to obtain a value in your designated 
unit, it is necessary to set Nc.  
Nc is a conversion coefcient for the ow and 
DP unit that is designated to be used.
(5) Selection of the Kfactor equation and calculation 
Select the Kfactor expression according to the 
uid type and the unit category shown in Table 
2.1.  
Calculate the Kfactor using the parameters and 
the expression.










