<10. General Specications>
10-1
IM 01C25R03-01E
10. General Specications
10.1 Standard Specications
For items other than those described below,
refer to each User’s Manual.
Applicable Model:
EJX910A and EJX930A
Output:
Digital communication signal based on
FOUNDATION Fieldbus protocol.
Supply Voltage:
9 to 32 V DC for general use, ameproof type
and Type n
Communication Requirements:
Supply Voltage: 9 to 32 V DC
Current Draw (Stedy state): 15 mA (max)
Current Draw (Software Download state):
24 mA (max)
Response Time (for Primary Value)
EJX910A L, M and H capsule 300 ms
EJX930A M and H capsule 350 ms
When amplier damping is set to zero, and
including dead time.
Update Period:
Differential Pressure: 200 ms
Static Pressure: 200 ms
Capsule Temperature: 1 s
Amplier Temperature: 1 s
External Temperature: 800 ms
Flow: 200 ms
Integral Indicator (LCD display)
5-digit Numerical Display, 6-digit Unit Display
and Bar graph. The indicator is congurable
to display one or up to ten of the I/O signals
periodically.
Functional Specications:
Functional specications for Fieldbus
communication conform to the standard
specications (H1) of FOUNDATION Fieldbus.
Function Block:
Block
name
Number
Execution
time
Note
AI 5 30 mS
For differential pressure,
static pressure and
temperature
SC 1 30 mS
An Output of Signal
Characterizer block is a
non-linear function of the
respective input. The function
is determined by a table
IT 1 30 mS
Integrator block integrates
a variable as a function of
the time or accumulates the
counts
IS 1 30 mS
Input Selector block provides
selection of up to eight inputs
and generate an output
based on the congured
action
AR 1 30 mS
Arithmetic block permits
simple use of popular
measurement math functions
PID 1 45 mS
Applicable when LC1 option
is specied
LM Function:
LM function is supported.
LM function is disabled when shipped.