<9. Parameter Lists>
9-7
IM 01C25R03-01E
Relative
Index
Index Parameter Name Factory Default
Write
Mode
Explanation
9 2309 TRANSDUCER_
DIRECTORY
— — This parameter is for storing the index of the transducer to be
included in the transmitter.
10 2310 TRANSDUCER_TYPE 104 (Standard
Flow with
Calibration)
— Indicates the type of transmitter.
11 2311 XD_ERROR — — Stores the most important error among the errors currently
occurring in the transducer block.
When “0” is stored, this means that no errors are occurring.
12 2312 COLLECTION_
DIRECTORY
— — Stores the index of important parameters in the transducer
block and the item ID of the corresponding DD.
13 2313 FLOW_VALUE_TYPE 1 — Indicates the type of ow.
1: Mass ow
2: Volume ow
3: Standard volume ow
14 2314 FLOW_VALUE — — Indicates the ow value and its status.
15 2315 FLOW_VALUE_UNIT 1324: kg/h — Indicates the unit of the ow value.
16 2316 FLOW_VALUE_
DECIMAL
0 — Indicates the number of digits past the decimal point of the ow
value.
17 2317 FLOW_VALUE_FTIME 0 O/S Indicates the primary lter time constant (unit: seconds) of the
ow value.
18 2318 DIFF_PRESSURE — — Indicates the differential pressure value used in the ow
calculation and its status.
19 2319 DIFF_PRESSURE_
UNIT
1133 (kPa) O/S Sets the unit of the differential pressure value.
20 2320 STATIC_PRESSURE — — Indicates the static pressure value used in the ow calculation
and its status.
21 2321 STATIC_PRESSURE_
UNIT
1545 (MPaa) O/S Sets the unit of the static pressure value.
22 2322 EXT_TEMPERATURE — — Indicates the external temperature value used in the ow
calculation and its status.
23 2323 EXT_TEMPERAURE_
UNIT
1001 (°C) O/S Sets the unit of the external temperature value.
24 2324 FLOW_
CALCULATION_MODE
0 O/S Switches the ow calculation mode.
0: Auto Compensation Mode
1: Basic Mode
25 2325 FIXED_FLOW_VALUE 0 O/S Sets the ow calculation coefcient (Kfactor) used in the Basic
Mode.
26 2326 REF_STATIC_
PRESSURE
0.101325 O/S Sets the design reference static pressure value used in the
Basic Mode.
27 2327 REF_EXT_
TEMPERATURE
0 O/S Sets the design reference temperature value used in the Basic
Mode.
28 2328 TEMP_K1_FOR_
LIQUID
0 O/S Sets the temperature coefcient for density compensation used
when calculating the liquid ow in the Basic Mode.
29 2329 FLUID_TYPE_CODE 2 O/S Sets the uid code in the Basic Mode.
1: Liquid
2: Gas
30 2330 ALARM_SUM Alarm / Enable — Indicates the alarm state of the entire block.
31 2331 DENSITY_UNIT_
CODE
*1
1097 (kg/m
3
) O/S Indicates the density unit.
1097: kg/m
3
1107: lb/ft3
32 2332 LENGTH_UNIT_
CODE
*1
1010 (m) O/S Indicates the length unit.
1018: ft
1010: m
1019: in
1012: cm
1013: mm
33 2333 PRIMARY_DEVICE_
CODE
*1
2 O/S Indicates the diaphragm type code.
For details on type code, see Table 9.1.
34 2334 PRIMARY_DEVICE_
DIAMETER
*1
0.03162 O/S Indicates the diaphragm inner diameter.
35 2335 PRIMARY_DEVICE_
EXPANSION_COEF
*1
0.00001681 O/S Indicates the diaphragm linear expansion coefcient value.
36 2336 PRIMARY_
DEVICE_REF_
TEMPERATURE
*1
20 O/S Indicates the temperature during diaphragm inner diameter
measurement.
37 2337 PIPE_DIAMETER
*1
0.0527 O/S Indicates the pipe inner diameter.