Relative
Index
Index Parameter Name Factory Default
Write
Mode
Explanation
57 2057 FIXED_EXT_TEMP_
VALUE
20.0 O/S Sets the external temperature xed value.
58 2058 SIMULATE_MODE 0 AUTO This is the switch for enabling simulation.
0=Simulation OFF
1=Differential pressure signal simulation ON
2=Static pressure signal simulation ON
3=Differential pressure signal + static pressure signal
simulation ON
4=External temperature signal simulation ON
5=Differential pressure signal + external temperature signal
simulation ON
6=Static pressure signal + external temperature signal
simulation ON
7=Differential pressure signal + static pressure signal +
external temperature signal simulation ON
15=Differential pressure signal + static pressure signal +
external temperature signal (without damping processing)
simulation ON
59 2059 SIMULATE_DPRESS 0 AUTO Sets the differential pressure value and status for simulation.
60 2060 SIMULATE_SPRESS 0 AUTO Sets the static pressure value and status for simulation.
61 2061 SIMULATE_ETEMP 0 AUTO Sets the external temperature value and status for simulation.
62 2062 EXT_TEMP_
SENSOR_SN
space AUTO This parameter is for recording the serial No. of the external
temperature sensor.
63 2063 CLEAR_CAL 0 O/S Reset zero and span adjustment to factory calibrated values for
pressure, static pressure, external temperature and or all.
64 2064 CAP_TEMP_VAL Measured capsule temperature value and status.
65 2065 CAP_TEMP_RANGE -50.0 to 130.0°C High and low range limit values, engineering units, decimal
point place for capsule temperature.
66 2066 AMP_TEMP_VAL Measured Amplier temperature value and status.
67 2067 AMP_TEMP_RANGE -50.0 to 95.0°C High and low range limit values, engineering units, decimal
point place for Amplier temperature.
68 2068 MODEL Model code The model code.
69 2069 SPECIAL_ORDER_ID Special order
number
Identication number of special order.
70 2070 MANUFAC_DATE 0 O/S Date of production
71 2071 CAP_GASKET_MTL Depend on Specify O/S Material of capsule gasket
72 2072 FLANGE_MTL Depend on Specify O/S Material of ange
73 2073 D_VENT_PLUG Depend on Specify O/S Material of drain or vent plug
74 2074 FLANGE_TYPE Depend on Specify O/S Flange type
75 2075 REM_SEAL_ISOL_
MTL
Depend on Specify O/S Material of isolating diaphragms for remote seal
76 2076 FLANGE_SIZE Depend on Specify O/S Flange size
77 2077 REM_SEAL_NUM Depend on Specify O/S Number of remote seal
78 2078 REM_SEAL_FILL_
FLUID
Depend on Specify O/S Types of ll uid in remote seals.
79 2079 REM_SEAL_TYPE Depend on Specify O/S Types of remote seals
80 2080 ALARM_SUM Alarm Enable The current alert status, unacknowledged states, unreported
states, and disabled states of the alarms associated with the
function block.
81 2081 AUTO_RECOVERY 1 (ON) O/S Permission of auto recovery from sensor errors.
82 2082 MS_CODE Null Model sufx and codes.
83 2083 DIAG_MODE 0 (stop) AUTO Used for ILBD. Refer to A8.2.12
84 2084 DIAG_PERIOD 180 AUTO Used for ILBD. Refer to A8.2.12
85 2085 DIAG_PRI 1 AUTO Used for ILBD and Heat Trace Monitoring. Refer to A8.2.12
86 2086 DIAG_ERR Used for ILBD and Heat Trace Monitoring. Refer to A8.2.12
87 2087 DIAG_H_ALM Used for ILBD and Heat Trace Monitoring. Refer to A8.2.12
88 2088 DIAG_L_ALM Used for ILBD and Heat Trace Monitoring. Refer to A8.2.12
89 2089 DIAG_OPTION 0 AUTO Used for ILBD and Heat Trace Monitoring. Refer to A8.2.12
90 2090 REF_LIM_ FDPMIN 7.00E-10 AUTO Used for ILBD. Refer to A8.2.12
91 2091 REF_LIM_ FSPMIN 1.00E-10 AUTO Used for ILBD. Refer to A8.2.12
92 2092 REF_LIM_BLKFMAX 0.5 AUTO Used for ILBD. Refer to A8.2.12
93 2093 COMP_FLAG 0 (Compensation) AUTO Used for ILBD. Refer to A8.2.12
94 2094 DIAG_LIM (Note) AUTO Used for ILBD. Refer to A8.2.12