Manual

<8. Device Information>
8-5
IM 01C25R03-01E
LCD
Display
Cause of
Alarm
Resource of
Alarm
SENSOR TB FLOW TB
BLOCK_
ERR
BLOCK_
ERR
XD_
ERROR
PV.STATUS
SV.STATUS
TV.STATUS
EXT_TEMP_
VAL.STATUS
CAP_TEMP_
VAL.STATUS
AMP_TEMP_
VAL.STATUS
FLOW_
VALUE.
STATUS
AL.12
CAP.TMP
Capsule
Temperature is
out of range
UNCERTAIN
Subnormal
UNCERTAIN
Subnormal
UNCERTAIN:
Sensor
Conversion
not Accurate
UNCERTAIN:
Sensor
Conversion
not Accurate
AL.13
AMP.
TMP
Amplier
temperature
is outside the
measurement
range limit
UNCERTAIN:
Sensor
Conversion
not
Accurate
UNCERTAIN:
Sensor
Conversion
not Accurate
AL.14
EXT.TMP
External
temperature is
outside of the
range limit.
UNCERTAIN:
Sensor
Conversion
not Accurate
UNCERTAIN:
Sensor
Conversion
not Accurate
AL.20
NOT.RDY
No
communication
is found with
LAS.
AL.40
RS O/S
RESOURCE
block is in O/S
mode
Out of Service BAD:
Non-specic
BAD:
Non-specic
BAD:
Non-specic
BAD:
Non-specic
BAD:
Non-specic
BAD:
Non-specic
AL.41
TB O/S
SENSOR
transducer
block is in O/S
mode
Out of
Service
Out of
Service
BAD:Out of
Service
BAD:Out of
Service
BAD:Out of
Service
BAD:Out of
Service
BAD:Out of
Service
AL.42
TB O/S
FLOW
transducer
block is in O/S
mode
BAD:Out of
Service
AL.50
P.SDEV
P.ZDEV
Trimming
range error
for differential
pressure span
other Calibration
error
UNCERTAIN:
Engineering
Unit Range
Violation
AL.51
SP.SDEV
SP.ZDEV
Trimming range
error for static
pressure span
other Calibration
error
UNCERTAIN:
Engineering
Unit Range
Violation
AL.52
ET.SDEV
ET.ZDEV
Trimming
range error
for External
temperature
span
other Calibration
error
UNCERTAIN:
Engineering
Unit Range
Violation
AL.80
SNR.SIM
Simulation
mode
other Simulation
Enabled
AL.81
FLW.CFG
Flow
TBconguration
error
AL.82
FLW.ALG
Flow correction
coefcient error
BAD:
Conguration
Error
AL.83
FLW.
SUM
Flow check
sum error
BAD:
Conguration
Error
*1: Good(NC) Non-specic for when Fall Back mode is selected for External Temperature and while xed temperature is output.
Table 8.10 Action of each parameters in failure mode related LCD display
ALARM
Display
Cause of Alarm
LCD TB
BLOCK_ERR XD_ERROR
AL.79
LCD.RNG
LCD.CFG
Displayed value exceeds limit or LCD conguration error