Manual
<8. Device Information>
8-2
IM 01C25R03-01E
Table 8.3 Contents of DEVICE_STATUS_3
(index 1047)
Hexadecimal
Display through
DD
Description
0x80000000 Diff Pressure
outside Range
Limit (AL-10)
Input Pressure is outside
measurement range limit
of capsule
0x40000000 Static Pressure
outside Range
Limit (AL-11)
Static Pressure exceeds
limit
0x20000000 Capsule Temp
outside Range
Limit (AL-12)
Capsule Temperature is
out of range
0x10000000 Amp Temp outside
Range Limit
(AL-13)
Amplier Temperature is
out of range
0x08000000 External Temp
outside Range
Limit (AL-14)
External temperature is
out of range
0x00008000 The execution of
AI1 is not ready
(AL-20)
AI1 is not ready
0x00004000 AI1 Non-Scheduled
(AL-21)
AI1 block is not
scheduled
0x00002000 AI2 Non-Scheduled
(AL-22)
AI2 block is not
scheduled
0x00001000 AI3 Non-Scheduled
(AL-23)
AI3 block is not
scheduled
0x00000800 AI4 Non-Scheduled
(AL-24)
AI4 block is not
scheduled
0x00000400 AI5 Non-Scheduled
(AL-25)
AI5 block is not
scheduled
Table 8.4 Contents of DEVICE_STATUS_4
(index 1048)
Hexadecimal
Display through
DD
Description
0x80000000 AI1 Hi Hi Alarm
occurs (AL-30)
Hi_Hi Alarm occurs in AI1
Function block
0x40000000 AI1 Lo Lo Alarm
occurs (AL-30)
Lo_Lo Alarm occurs in
AI1 Function block
0x20000000 AI2 Hi Hi Alarm
occurs (AL-31)
Hi_Hi Alarm occurs in AI2
Function block
0x10000000 AI2 Lo Lo Alarm
occurs (AL-31)
Lo_Lo Alarm occurs in
AI2 Function block
0x08000000 AI3 Hi Hi Alarm
occurs (AL-32)
Hi_Hi Alarm occurs in AI3
Function block
0x04000000 AI3 Lo Lo Alarm
occurs (AL-32)
Lo_Lo Alarm occurs in
AI3 Function block
0x02000000 AI4 Hi Hi Alarm
occurs (AL-33)
Hi_Hi Alarm occurs in AI4
function block
0x01000000 AI4 Lo Lo Alarm
occurs (AL-33)
Lo_Lo Alarm occurs in
AI4 function block
0x00800000 AI5 Hi Hi Alarm
occurs (AL-34)
Hi_Hi Alarm occurs in AI5
function block
0x00400000 AI5 Lo Lo Alarm
occurs (AL-34)
Lo_Lo Alarm occurs in
AI5 function block
0x00200000 PID Hi Hi Alarm
occurs (AL-35)
Hi_Hi Alarm occurs in
PID Function block
0x00100000 PID Lo Lo Alarm
occurs (AL-35)
Lo_Lo Alarm occurs in
PID Function block
0x00008000 RB in O/S mode
(AL-40)
Resource Block is in O/S
mode
0x00004000 Sensor TB in O/S
mode (AL-41)
Sensor TB is in O/S
mode
0x00001000 Flow TB in O/S
mode (AL-42)
FLOW TB is in O/S mode
0x00000800 AI1 in O/S mode
(AL-43)
AI1 block is in O/S mode
0x00000400 AI2 in O/S mode
(AL-44)
AI2 block is in O/S mode
0x00000200 AI3 in O/S mode
(AL-45)
AI3 block is in O/S mode
0x00000100 AI4 in O/S mode
(AL-46)
AI4 block is in O/S mode
0x00000080 AI5 in O/S mode
(AL-47)