6.5 LCD Transducer Block
6.5.1 Outline of the Functions
The LCD transducer block controls alarms and
measured values that are displayed on the integral
indicator. It displays not only OUT signals from the
AI blocks, but also I/O signals of the Installed blocks
on the integral indicator.
6.5.2 Block Mode
The Block modes permitted for the LCD transducer
block are Automatic (Auto) and Out of Service (O/
S). Settings can be changed in the AUTO mode for
this block, except the Block tag parameter.
6.5.3 Display Contents of the Integral
Indicator
The components of the integral indicator are the bar
graph, the title eld, the center eld for numerical
values, the lower text eld, and auxiliary characters.
The contents and meanings of these components
are as follows:
F0605.ai
40.000
37.000
Figure 6.3 Screen Display of the integral indicator
Component
name
Contents
Bar graph Shows the value displayed in the center
eld for numerical values scaled in terms
of percentage.
Center eld
for numerical
values
Presents values of inputs and outputs.
While the alarm is on, the alarm number
alternates with the displayed value here.
Lower text
eld
Displays tag, parameter name, unit, and
signal status. While the alarm is on, the
alarm contents alternate.
Title eld Depicts the type of the value displayed
on the center eld for numerical value.
P Flashes when differential
pressure is displayed.
SP Flashes when static pressure is
displayed.
T Flashes when temperature is
displayed.
F Flashes when ow rate is
displayed.
Auxiliary
characters
% Flashes when the center eld
for numerical values displays a
% value.
Flashes when square root
display is selected.
Key
mark
Flashes when Write Protect is
selected.
×10,
×100,
×1000
Used when the calculated value
displayed in the center eld for
numerical values is rounded.