Manual
    <6.  Explanation of Basic Items>
6-4
IM 01C25R03-01E
F0604.ai
0
0
Calculated Value Calculated Value
Span 
adjustmen
point
After zero 
adjustment 
After zero adjustment 
After zero/span
adjustment
Input pressure Input pressure
Before zero 
adjustment
CAUTION
Span adjustment is a function for adjusting 
the gradient with respect to the point of zero 
adjustment.  If that point is not zero, the gradient 
of input and output values cannot be accurately 
adjusted. Perform span adjustment after zero 
adjustment is completed.
Diagnosis of adjustment results:
When the amount of zero adjustment or span 
adjustment exceeds any of the following adjustment 
limits, “AL50: Adjustment range error for differential 
pressure” is displayed.
The conditions for zero/span adjustment are as 
follows:
<1> The point of zero adjustment is within 
±10% of the capsule range.
<2> The amount of zero adjustment is within 
±10% of the capsule range.
<3> The point of span adjustment is within the 
capsule range.
<4> The input and output gradients after span 
adjustment are within ±10% of the gradient at 
factory setting.
6.3.4  Functions Relating to Static 
Pressure
Reference to static pressure value:
In SECONDARY_VALUE and TERTIARY_VALUE, 
it is possible to refer to the H-side static pressure 
value and the L-side static pressure value, 
respectively. The update period of these values 
is 200 mseconds. The pressure unit is selected 
by XD_SCALE.unit in the AI block, in which 
SECONDARY_VALUE and TERTIARY_VALUE 
are selected.  The status is normally Good-Non 
Specic.  However, in the case of a sensor failure 
or out of measurement range, it turns to Bad or 
Uncertain.  For specics, refer to Table 8.9.
Setting of signal damping for static pressure:
SP_VALUE_FTIME is parameter that set signal 
damping for static pressure signals. The unit of the 
signal damping is second.
Determination of the range limit of static 
pressure signal:
When the static pressure signal exceeds the 
maximum working pressure (MWP) of the capsule, 
set the status of PRIMARY_VALUE to Uncertain-
Subnormal. Also, set the status of SECONDARY_
VALUE and TERTIARY_VALUE to Uncertain-
Sensor Conversion not Accurate. The status under 
normal conditions is Good-Non Specic.
Adjustment of static pressure signal:
The zero/span adjustment function can be used for 
static signals, as in the case of differential pressure 
signals. However, the zero-point adjustment by the 
external screw function is not supported for static 
pressure signal.
Automatic adjustment
The value of the static pressure exerted on the 
point where adjustment is to be made is assigned 
to parameters (CAL_SP_POINT_LO, CAL_SP_
POINT_HI). After this assignment is set, the amount 
of adjustment is calculated by the transmitter and 
automatically updated. The procedure for adjusting 
the static pressure signal is the same as that of 
differential pressure signal.
Manual adjustment
From the exerted pressure and the output of the 
transmitter, calculate the amount of zero/span 
adjustment manually and assign the calculated 
value to parameters (CAL_SP_DEVIATION_LO, 
CAL_SP_DEVIATION_HI).
Selection of static pressure signal type:
EJX910 multivariable transmitter measure the 
absolute static pressure. Based on the assumption 
that atmospheric pressure is constant, these 
transmitters can output signal equivalent to gauge 
pressure calculated by deducting the atmospheric 
pressure (xed value) from the measured absolute 
pressure. The type of static pressure signal output 
to SECONDARY_VALUE and TERTIARY_VALUE 
is selected in SP_VALUE_TYPE.  SP_VALUE_
TYPE allows selection of gauge pressure or 
absolute pressure. When selecting gauge pressure, 
set the value of the atmospheric pressure (xed 
value) to ATM_PRESS. The default value of 
ATM_PRESS is equal to the value of standard 
atmospheric pressure (101.325 kPa). 










